2.6 Working State
The series inverter has Waiting, Checking, Normal, EPS Checking, EPS, Fault, Idle and
Standby state.
Table 2-3 Description of working state
State Description
Waiting
The inverter is waiting for the following two conditions to be met
in order to enter the Checking state
:
• The adequate photovoltaic input voltage.
• The AC side voltage and frequency meet the grid requirements
specified by the grid regulations.
Checking
• The inverter is checking for conditions to enter Normal state.
Normal • The inverter is working normally.
EPS Checking • The inverter is checking for conditions to enter EPS state.
EPS • The inverter is working in off-grid state.
Fault • The inverter detects error occured and prompts error code.
Idle
• The battery SOC reaches the minimum SOC and there is no
sufficient PV input voltage, etc.
Unusual Idle
• The battery needs to be charged but PV and grid power are not
allowed to charge the battery
Standby
• A standby state when the power of load is extremely low and
there is no sufficient PV input voltage, or a state when the battery
SOC is more 10% and there is no sufficient PV input voltage.
• In this state, it detects PV connection, load power, etc to
determine whether to exit Standby state and enter Normal state.
NOTICE!
• When the inverter is in an Idle state, you can reset the work mode, the Min SOC and
the charging periods through the inverter LCD or the SolaX APP to charge the battery
to the Min SOC in the charging periods and then awaken the inverter. Please make
sure that the actual battery SOC - the modified Min SOC ≥ 2% under a specific work
mode, so that other modifications are effective. When the current system time is
within the new charing periods you reset, the battery begins charing.