89
Operation on LCD
Setting Self Use Mode
Please refer to "2.7.1 Self-use Mode" for working logic of this mode.
• Min SOC: Default: 10%; range: 10%~100%
»
The minimum SOC of the battery. The battery will not discharge power when
the SOC of the battery reaches this value.
=====User Setting=====
EPS Mute
>Self Use Mode
Feed-in Priority
====Self Use Mode====
>Min SoC
10%
• Charge from grid:
»
You can set whether to draw electricity from the grid to charge the battery
during the forced charging period. When Charge from grid is set to Enable,
the utility power is allowed to charge the battery; when it is set to Disable,
the utility power is not allowed to charge the battery.
====Self Use Mode====
Min SoC
>Charge from grid
====Self Use Mode====
Charge from grid:
> Enable <
• Charge battery to: Default: 30%; range: 10%~100%
»
Set the SOC target value for charging the battery from grid during the forced
charging period (applicable only when the Charge from grid is enabled).
»
You can set your own target value, i.e. during the forced charging period,
the inverter will use both PV & GRID energy to charge the battery SOC to
the target SOC value+5%, after the battery SOC meets the target value, if the
PV energy is still sufficient (enough for load and there is excess power), the
inverter will continue to use PV energy to charge the battery.
====Self Use Mode====
>Charge battery to
30%
Setting Feed-in Priority
Please refer to "2.7.2 Feed-in Priority" for working logic of this mode.
• Min SOC: Default: 10%; range: 10%~100%
»
The minimum SOC of the battery. The battery will not discharge power when
the SOC of the battery reaches this value.
=====User Setting=====
Self Use Mode
>Feed-in Priority
Backup Mode
====Feedin Priority====
>Min SoC
10%
• Charge battery to: Default: 50%; range: 10%~100%