20 • Installation
________________________________________________________________________________________________
For other models dimensions – consult factory.
6. INSTALLATION
WARNING!
Do not interchange line and load connections
6.1 Prior to Installation
Check that LOAD RATED CURRENT (FLA) is lower than, or equal, to the TPS RATED CURRENT.
Note:
TPS RATED CURRENT (FLC) LOAD RATED CURRENT In all 3 phases!!
Check that Mains and Control voltages are as indicated on the TPS side label.
Make sure TPS RATED CURRENT(FLC) LOAD
RATED CURRENT! (In all 3 phases)
Make sure Mains voltage is right!
Make sure Control voltage is right!
TPS label - example
6.2 Mounting
The TPS must be mounted vertically. Allow sufficient space (at least 100mm) above and below the TPS for
suitable airflow.
It is recommended to mount the TPS directly on the rear metal plate for better heat dissipation.
Note:
Do not mount the TPS directly on the rear metal plate in case a ventilation fan or ventilation opening is on the
back side of the TPS.
Do not mount the TPS near heat sources.
Surrounding air temperature in the cabinet should not exceed 50ºC
Protect the TPS from dust and corrosive atmospheres.
Note: For harsh environments, it is recommended to order the TPS with printed circuit board coating. Refer to
section Error! Reference source not found. on page Error! Bookmark not defined. for ordering
information.
6.3 Temperature range & heat dissipation
The TPS is rated to operate over a temperature range of -10ºC (14ºF) to + 50ºC (122ºF).
Relative non-condensed humidity inside the enclosure should not exceed 95%.
ATTENTION!
Operating at surrounding air temp. (Inside the cabinet) higher than 50ºC may
cause damage to the TPS.
Heat Dissipation is:
1.3x3xI+FAN and TPS consumption rating
Where:
I is the RMS current of the TPS.
FAN and TPS consumption rating - is shown on the technical specifications page 42.
So, for example, the maximum heat dissipation for a 210A TPS is: 1.3x3x210+64=883Watt.
6.4 Protection bus-bars covers for power terminals.
Protection bus-bars covers can be fitted with power terminals.
Consult factory for this option.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Solcon TPS and is the answer not in the manual?

Solcon TPS Specifications

General Specifications IconGeneral Specifications
rated current8-1500A
rated voltage120 - 1000VAC +10% -15%
control voltage120 or 230VAC, 110VDC+10% -15%
frequency50 / 60 Hz
controlled phasesThree
short-circuit current25kA
rated insulation voltage690V (120-690V mains models), 1000V (1000V mains models), 250V (control circuits)
rated impulse withstand6kV (Mains), 2.5kV (control)
degree of protectionIP00
pollution degree3
ambient temperature operating-10 – + 50°C
ambient temperature storage-20 – + 70°C
altitudeTo 1000 m ASL W/O de-rating
coolingForced air (fans)
number of CTsThree
connection modesWye - Neutral connected / not connected
Control Specifications IconControl Specifications
control methodDigital
firing methodZero crossing, Phase control, Phase control-power
on-off time cycle1000 – 10000 mSec.
analog input0-10V >100KΩ / 4-20 mA, 0-20mA <100Ω
control inputsStart/Stop (with internal 0-60 sec time delays), Aux. contact
output relays3 programmable (1-C/O) (8A/250VAC)
maximum breaking capacity AC2000 VA
max. DC load breaking capacity8A at 30VDC.
synchronizationOne master and 2-9 connected slaves
Fan and TPS Consumption Ratings IconFan and TPS Consumption Ratings
TPS 8-31A consumption21W
TPS 44-72A consumption36W
TPS 85-105A consumption26W
TPS 145-170A consumption35W
TPS 210-460A consumption64W
TPS 580-820A consumption100W
TPS 55-200A 1000V consumption40W

Related product manuals