21 • Installation
________________________________________________________________________________________________
6.5 Jumpers settings for analogue input configuration
See next page for jumpers location.
The TPS incorporates 4 jumpers which configure terminals 16 & 17 to work as a voltage reference input,
current reference input or voltage free potentiometer input.
Jumpers must be set correctly prior to start up.
Caution:
Damage may occur if jumpers are not properly set
The jumpers are located on the main PCB (Refer to control module picture on page 22) and should be set as
follows:
Description Use
JP1 and JP2 are closed
JP3 and JP4 are open.
* This is factory default
setting.
Use when 0-20mA or 4-20mA is connected to terminals 16 &
17. Refer to section
7.7.2 on page 30 for programming TPS
ANALOG IN TYPE.
JP3 and JP4 are closed.
JP1 and JP2 are open.
Use when 0-10V is connected to terminals 16 & 17. Refer to
section
7.7.2 on page 30 for programming TPS ANALOG IN
TYPE.
JP4 is closed.
JP1, JP2 and JP3 are open.
Use when potentiometer input is connected to terminals 16 &
17 and 20. TPS must be programmed as “voltage input” 0..10V.
Refer to section
7.7.2 on page 30 for programming TPS
ANALOG IN TYPE.
Note:
- Indicates closed jumper.
- Indicates open jumper.
6.6 Dip switches settings for analogue output optional PCB
See next page for analogue output optional PCB location.
Analogue P.C.B. layout
Analogue Output ( terminals Out (+), Out (-))
Dip switches allow selection between: 0-10VDC, 0-20mA, 4-20mA

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Solcon TPS and is the answer not in the manual?

Solcon TPS Specifications

General Specifications IconGeneral Specifications
rated current8-1500A
rated voltage120 - 1000VAC +10% -15%
control voltage120 or 230VAC, 110VDC+10% -15%
frequency50 / 60 Hz
controlled phasesThree
short-circuit current25kA
rated insulation voltage690V (120-690V mains models), 1000V (1000V mains models), 250V (control circuits)
rated impulse withstand6kV (Mains), 2.5kV (control)
degree of protectionIP00
pollution degree3
ambient temperature operating-10 – + 50°C
ambient temperature storage-20 – + 70°C
altitudeTo 1000 m ASL W/O de-rating
coolingForced air (fans)
number of CTsThree
connection modesWye - Neutral connected / not connected
Control Specifications IconControl Specifications
control methodDigital
firing methodZero crossing, Phase control, Phase control-power
on-off time cycle1000 – 10000 mSec.
analog input0-10V >100KΩ / 4-20 mA, 0-20mA <100Ω
control inputsStart/Stop (with internal 0-60 sec time delays), Aux. contact
output relays3 programmable (1-C/O) (8A/250VAC)
maximum breaking capacity AC2000 VA
max. DC load breaking capacity8A at 30VDC.
synchronizationOne master and 2-9 connected slaves
Fan and TPS Consumption Ratings IconFan and TPS Consumption Ratings
TPS 8-31A consumption21W
TPS 44-72A consumption36W
TPS 85-105A consumption26W
TPS 145-170A consumption35W
TPS 210-460A consumption64W
TPS 580-820A consumption100W
TPS 55-200A 1000V consumption40W