24 • Control Keypad
________________________________________________________________________________________________
7.3 Status LEDs.
Green
On
Lights when Control Supply voltage is connected to the TPS
Red
Stop
Lights when TPS is in stop condition. (Before RUN command is initiated)
Green
Run
Lights when TPS is feeding the load.
Yellow
Alarm
Lights during alarm condition.
Note: LED can be latched on/off as per AUTO RESET ENABLE/DISABLE setting.
Refer to section
7.7.5 page 35.
Red
Trip
Lights during trip condition.
Note: LED can be latched on/off as per AUTO RESET ENABLE/DISABLE setting.
Refer to section
7.7.5 page 35.
Green
Sync.
Lights when TPS is programmed to MASTER or SLAVE mode of operation.
Refer to section
3.9 page 11 for more details.
7.4 Reviewing and modifying parameters
Press Page key several times until you reach the required Mode page.
Press Select key to review parameters of this Mode.
When reaching the required parameter, modify its values with or keys.
Once value is set press Store key. Once data was properly stored in the non-volatile memory, the LCD will
display DATA SAVED OK for 2 seconds.
In addition the modified parameter/s can be stored at the end of every mode page. Press Select until “STORE
ENABLE To store the new parameters, press Select key until STORE ENABLE XXX PARAMETERS, then
press Store key. The LCD will display DATA SAVED OK for 2 seconds.
7.5 Special actions performed by the key-pad.
7.5.1 Run self test, Software version, default parameters and clear statistical data
Press Page and keys simultaneously.
The LCD will display:
TEST / MAINTENANCE
******OPTIONS***********
Press Select key.
The LCD will display:
RUN SELF TEST?
PUSH UP ARROW
To perform a self test push UP ARROW.
If self test OK, display will show:
SELF TEST PASSED
Press Select key.
The LCD will display the software version:
BTL-15/05/2009
TPS-230113noSTAT
Press Select key.
The LCD will display:
STORE NOW?
DEFAULT PARAMETERS
To obtain “default parameters” press Page+Store Simultaneously.