36 • Control Keypad
________________________________________________________________________________________________
7.7.6 Comm. Parameters – page 6
COMM.PARAMETERS
SETTINGS
Display and default
values
Range Description
COMM. PROTOCOL
MODBUS
MODBUS Sets TPS communication PROTOCOL.
Available only when Communication card is installed.
BAUD RATE
19200
1200, 2400,
4800, 9600,
19200
Sets TPS BAUD RATE.
Available only when Communication card is installed.
PARITY CHECK
EVEN
EVEN, ODD,
NONE
Sets TPS communication PARITY CHECK.
Available only when Communication card is installed.
SERIAL LINK NO.
248 (OFF)
1 – 248 (off) Sets TPS communication SERIAL LINK NO.
Available only when Communication card is installed.
S.LINK PAR. SAVE
DISABLE
ENABLE
DISABLE
When set to DISABLE, it prevents parameter setting
through serial link communication.
When set to Enable, parameter setting through serial link is
enabled.
SER.LINK CONTROL
DISABLE
DISABLE
ATART/STOP
FULL
When DISABLE is selected control via serial link is not
possible.
When START/STOP is selected, a START, STOP and
RESET commands can be initiated via the serial link.
When FULL is selected, all commands as in START/STOP
option can be initiated via the serial link and, in addition, the
value of the analog input is taken from the serial link.
Note:
When FULL option is selected, the wired analog input
(Terminals 16, 17 and 20) of the TPS is not active.
STORE ENABLE
COMM. PARAMETERS
Same as STORE ENABLE MAIN PARAMETERS
On page 29.