31 • Control Keypad
________________________________________________________________________________________________
I/O PARAMETERS
SETTINGS
CONFIG OUT B
ALARM-FAIL SAFE
Same as CONFIG OUT
A – See above.
Sets TPS functions of output relay B (Terminals 10,
11, 12)
Same as CONFIG OUT A – See above.
OUT B RELAY DLY
0.0 SEC.
0.0 SEC.-60.0 SEC. Sets delay time for this OUT RELAY.
CONFIG OUT C
TRIP
Same as CONFIG OUT
A – See above.
Sets TPS functions of output relay C (Terminals 13,
14, 15)
Same as CONFIG OUT A – See above.
OUT C RELAY DLY
0.0 SEC.
0.0 SEC.-60.0 SEC. Sets delay time for this OUT RELAY.
KWH PER PULSE
OFF
OFF, 1KWH - 100KWH Sets KWH/Pulse for KWH metering. OUT A or OUT B
or OUT C must be programmed to KWH PULSE
RELAY in order that this function will be effective.
(See above)
AN. OUT PARAMETER
P, 0-100% OF Pn
P, 0-100% OF Pn
I, 0-100% OF FLA.
I1, 0-100% OF FLA.
I2, 0-100% OF FLA.
I3, 0-100% OF FLA.
ANALOG INPUT
Sets TPS analogue output (optional). (Terminals
out(+), out(-).
Dip switches on the analogue output PCB allow
selection between: 0-10VDC, 0-20mA, 4-20mA
Refer to section
6.6 page 21 for dip switch settings.
P, 0-100% OF Pn - is programmed when analogue
output is related to Pn.
I, 0-100% OF FLA - is programmed when analogue
output is related to average I as a percentage of
LOAD RATED CURRENT.
I1(I2, I3), 0-100% OF FLA - is programmed when
analogue output is related to I1 (I2, I3) as a
percentage of LOAD RATED CURRENT.
ANALOG INPUT - is programmed when analogue
output is a reflection of analogue input.
STORE ENABLE
I/O PARAMETERS
Same as STORE ENABLE MAIN PARAMETERS
On page 29.