31 • Control Keypad
________________________________________________________________________________________________
I/O PARAMETERS
SETTINGS
CONFIG OUT B
ALARM-FAIL SAFE
Same as CONFIG OUT
A – See above.
Sets TPS functions of output relay B (Terminals 10,
11, 12)
Same as CONFIG OUT A – See above.
OUT B RELAY DLY
0.0 SEC.
0.0 SEC.-60.0 SEC. Sets delay time for this OUT RELAY.
CONFIG OUT C
TRIP
Same as CONFIG OUT
A – See above.
Sets TPS functions of output relay C (Terminals 13,
14, 15)
Same as CONFIG OUT A – See above.
OUT C RELAY DLY
0.0 SEC.
0.0 SEC.-60.0 SEC. Sets delay time for this OUT RELAY.
KWH PER PULSE
OFF
OFF, 1KWH - 100KWH Sets KWH/Pulse for KWH metering. OUT A or OUT B
or OUT C must be programmed to KWH PULSE
RELAY in order that this function will be effective.
(See above)
AN. OUT PARAMETER
P, 0-100% OF Pn
P, 0-100% OF Pn
I, 0-100% OF FLA.
I1, 0-100% OF FLA.
I2, 0-100% OF FLA.
I3, 0-100% OF FLA.
ANALOG INPUT
Sets TPS analogue output (optional). (Terminals
out(+), out(-).
Dip switches on the analogue output PCB allow
selection between: 0-10VDC, 0-20mA, 4-20mA
Refer to section
6.6 page 21 for dip switch settings.
P, 0-100% OF Pn - is programmed when analogue
output is related to Pn.
I, 0-100% OF FLA - is programmed when analogue
output is related to average I as a percentage of
LOAD RATED CURRENT.
I1(I2, I3), 0-100% OF FLA - is programmed when
analogue output is related to I1 (I2, I3) as a
percentage of LOAD RATED CURRENT.
ANALOG INPUT - is programmed when analogue
output is a reflection of analogue input.
STORE ENABLE
I/O PARAMETERS
Same as STORE ENABLE MAIN PARAMETERS
On page 29.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Solcon TPS and is the answer not in the manual?

Solcon TPS Specifications

General Specifications IconGeneral Specifications
rated current8-1500A
rated voltage120 - 1000VAC +10% -15%
control voltage120 or 230VAC, 110VDC+10% -15%
frequency50 / 60 Hz
controlled phasesThree
short-circuit current25kA
rated insulation voltage690V (120-690V mains models), 1000V (1000V mains models), 250V (control circuits)
rated impulse withstand6kV (Mains), 2.5kV (control)
degree of protectionIP00
pollution degree3
ambient temperature operating-10 – + 50°C
ambient temperature storage-20 – + 70°C
altitudeTo 1000 m ASL W/O de-rating
coolingForced air (fans)
number of CTsThree
connection modesWye - Neutral connected / not connected
Control Specifications IconControl Specifications
control methodDigital
firing methodZero crossing, Phase control, Phase control-power
on-off time cycle1000 – 10000 mSec.
analog input0-10V >100KΩ / 4-20 mA, 0-20mA <100Ω
control inputsStart/Stop (with internal 0-60 sec time delays), Aux. contact
output relays3 programmable (1-C/O) (8A/250VAC)
maximum breaking capacity AC2000 VA
max. DC load breaking capacity8A at 30VDC.
synchronizationOne master and 2-9 connected slaves
Fan and TPS Consumption Ratings IconFan and TPS Consumption Ratings
TPS 8-31A consumption21W
TPS 44-72A consumption36W
TPS 85-105A consumption26W
TPS 145-170A consumption35W
TPS 210-460A consumption64W
TPS 580-820A consumption100W
TPS 55-200A 1000V consumption40W