Frequency Inverter ST600 Series High-Performance Multifunction VFD Function parameter list
-135-
P00––Basic functions
0: SVC 0
1: SVC 1
2: SVPWM
3: FVC
Note: If 0, 1 or 3 is selected, it is required to carry out motor
parameter autotuning first.
0: Keypad
1: Terminal
2: Communication
Communication
running
command
channel
0: Modbus/Modbus TCP
1: PROFIBUS/CANopen/DeviceNet
2: Ethernet
3: EtherCAT/PROFITNET/Ethernet IP
4: PLC programmable card
5: Wireless communication card
Note: Modbus TCP, 1, 2, 3, 4 and 5 are extended functions
which are applicable with corresponding cards.
Used to set the max. output frequency of the VFD. It is the
basis of frequency setup and the acceleration/deceleration.
Setting range: Max (P00.04, 10.00) –630.00Hz
Upper limit of
running
frequency
The upper limit of running frequency is upper limit value of
VFD output frequency. This value should be no more than
the max. output frequency.
When the set frequency is higher than the upper limit
frequency, the VFD runs at the upper limit frequency.
Setting range: P00.05–P00.03 (max. output frequency)
Lower limit of
running
frequency
The lower limit of running frequency is the lower limit value
of VFD output frequency.
When the set frequency is lower than the lower limit
frequency, the VFD runs at the lower limit frequency.
Note: Max. output frequency ≥ upper limit frequency ≥ lower
limit frequency.
Setting range: 0.00Hz–P00.04 (upper limit of running
frequency)
A frequency
command
selection
0: Keypad
1: AI1
2: AI2
3: AI3
4: High speed pulse HDIA
5: Simple PLC program
6: Multi-step speed running
7: PID control
8: Modbus/Modbus TCP communication
9: PROFIBUS/CANopen/DeviceNet communication
B frequency
command
selection