EasyManua.ls Logo

Sourcetronic ST600 - Motor Parameter

Sourcetronic ST600
390 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Frequency Inverter ST600 Series High-Performance Multifunction VFD Basic Operation Instructions
-76-
5.5.6 Motor parameter
Check the safety conditions surrounding the motor and load machineries before
autotuning as physical injury may occur due to sudden start of motor during autotuning.
Although the motor does not run during static autotuning, the motor is stilled supplied
with power, do not touch the motor during autotuning; otherwise electric shock may
occur.
If the motor has been connected to load, do not carry out rotary autotuning; otherwise
malfunction or damage may occur to the VFD. If rotary autotuning is carried out on a motor
which has been connected to load, wrong motor parameters and motor misacts may occur.
Disconnect the load to carry out autotuning if necessary.
The ST600 Series VFD can drive asynchronous motors and synchronous motors, and it supports two
sets of motor parameters, which can be switched over by multi-function digital input terminals or
communication modes.
Communication
(P00.01=2)
Terminal
(P00.01=1)
Keypad
(P00.01=0)
Modbus/
Modbus TCP
communication
PROFIBUS/
CANopen/
DeviceNet
communication
Start
Select running
command channel
(P00.01)
Switchover
channel for motor 1 and
motor 2
(P08.31)
Terminal function 35
Switch motor 1 to
motor 2
Communication set value
2009H
Motor 1 Motor 2
Invalid
Valid
BIT01=00
BIT01=01
P08.31 ones = 0
Ethernet
communication
P08.31 ones = 1
P08.31 ones = 2 P08.31ones = 3
EtherCAT/PROFINET/
EtherNet IP
communication
P08.31 ones = 4
The control performance of the VFD is based on accurate motor model, therefore, users need to carry
out motor parameter autotuning before running the motor for the first time (take motor 1 as an example)

Table of Contents

Other manuals for Sourcetronic ST600

Related product manuals