Frequency Inverter ST600 Series High-Performance Multifunction VFD Basic Operation Instructions
-97-
P06.28
Corresponding HDO output of
lower limit
0.00–50.00kHz
0.0kHz
P06.29
Upper limit of HDO output
P06.27–300.0%
100.0%
P06.30
Corresponding HDO output of
upper limit
0.00–50.00kHz
50.00kHz
P06.31
HDO output filter time
0.000s–10.000s
0.000s
5.5.11 Digital input
The ST600 Series VFD carries four programmable digital input terminals and two HDI input terminals.
The function of all the digital input terminals can be programmed by function codes. HDI input terminal
can be set to act as high-speed pulse input terminal or common digital input terminal; if it is set to act
as high-speed pulse input terminal, users can also set HDIA or HDIB high-speed pulse input to serve
as the frequency reference and encoder signal input.
S1
S2
S3
S4
HDIA
HD1B
P05.08 (input terminal polarity)
P05.01
P05.02
P05.03
P05.04
T delay
T delay
T delay
T delay
T delay
T delay
P05.13
P05.15
P05.17
P05.19
P05.21
P05.23
0
1
2
3
4
5
.
.
.
.
29
30
P05.09 (digital filter time)
(Default value is 1)
(Default value is 4)
(Default value is 7)
(Default value is 0)
(Default value is 0)
(Default value is 0)
P05.00
(HDI input type)
0
1
0
1
-1
0
1
-1
0
1
-1
0
1
-1
0
1
-1
0
1
-1
P17.12
Digital input
terminal state
P07.39
Input terminal
state of present
fault
Fault?
Fault
Run
Digital function selection
T delay
T delay
T delay
T delay
T delay
T delay
P05.12
P05.14
P05.16
P05.18
P05.20
P05.22
P05.05
P05.06
This parameter is used to set the corresponding function of digital multi-function input terminals.
Note: Two different multi-function input terminals cannot be set to the same function.
Set
value
Function
Description
0
No function
The VFD does not act even if there is signal input; users can
set the unused terminals to "no function" to avoid misacts.
1
Forward running (FWD)
Control the forward/reverse running of the VFD by external
terminals.
2
Reverse running (REV)
3
3-wire control
Set the VFD running mode to the 3-wire control mode by this
terminal. See P05.13 for details.
4
Forward jogging
Frequency when jogging, see P08.06, P08.07 and P08.08 for
jogging acceleration/deceleration time.
5
Reverse jogging