Frequency Inverter ST600 Series High-Performance Multifunction VFD Installation Guide
-37-
Max. input frequency: 50kHz;
Duty ratio: 30%–70%;
Supports the input of a quadrature encoder with 24V power supply; equipped with speed-
measurement function
1. Safe torque off (STO) redundant input, connect to external NC
contact, STO acts when the contact opens, and the VFD stops output;
2. Safety input signal wires use shielded wire whose length is within
25m;
3. H1 and H2 terminals are short connected to +24V by default; it is
required to remove the jumper on the terminal before using STO
function.
4.4.2 Input/output signal connection diagram
Set NPN/PNP mode and internal/external power via U-shaped jumper. PNP internal mode is adopted
by default.
Figure 4-29 Position of U-shaped jumper (standard models)
U-type short-
contact tag of H2
and +24V
U-type short-contact
tag of COM and
+CME
U-type short-
contact tag of
+24V and PW
U-type short-
contact tag of H1
and +24V
+24V
485++24V CME 485-485GCOMCOMPE H2
R01CR02C
H1 +24V
R01BR02B
PW COM HDO Y1 AO1 GND
S1 S2 S3 S4 HDIA HDIB AI1 AI2 +10V
R01AR02A
USB port
Keypad port
Figure 4-30 Position of U-shaped jumper (SP models)
U-shaped jumper
between H2 and
+24V
U-shaped jumper
between COM and
CME
U-shaped jumper
between PW and
COM
U-shaped jumper
between H1 and
+24V
+24V
485++24V CME 485-COMCOMPE H2
R01CR02C
H1 +24V
R01BR02B
PW COM HDO Y1 AO1GND
S1 S2 S3 S4 HDIA HDIB AI1 AI2 +10V
R01AR02A
If input signal comes from NPN transistors, set the U-shaped jumper between +24V and PW based