EasyManua.ls Logo

Sourcetronic ST600 - Page 43

Sourcetronic ST600
390 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Frequency Inverter ST600 Series High-Performance Multifunction VFD Installation Guide
-36-
Terminal name
Instruction
+10V
The VFD provides +10.5V power
AI1
1. Input range: AI1 voltage/current can choose 010/ 020mA; AI2: -10V+10V voltage;
2. Input impedance: 20kΩ during voltage input; 250Ω during current input;
3. AI1 voltage or current input is set by P05.50;
4. Resolution ratio: When 10V corresponds to 50Hz, the min. resolution ratio is 5mV;
5. 25°C, When input above 5V or 10mA, the error is ±0.5%
AI2
GND
Reference ground of +10.5V
AO1
1. Output range: 010V voltage or 020mA current
2. Voltage or current output is set by toggle switch SW2;
3. 25°C, when input above 5V or 10mA, the error is ±0.5%.
RO1A
RO1 relay output; RO1A is NO, RO1B is NC, RO1C is common port
Contact capacity: 3A/AC250V, 1A/DC30V
RO1B
RO1C
RO2A
RO2 relay output; RO2A is NO, RO2B is NC, RO2C is common port
Contact capacity: 3A/AC250V, 1A/DC30V
RO2B
RO2C
HDO
1. Switch capacity: 50mA/30V;
2. Range of output frequency: 050kHz
3. Duty ratio: 50%
COM
Reference ground of +24V
CME
Common port of open collector output; short connected to COM by default
Y1
1. Switch capacity: 50mA/30V;
2. Range of output frequency: 0–1kHz
485+
485 communication port, 485 differential signal port and standard 485 communication
interface should use shielded twisted pair; the 120Ω terminal matching resistor of 485
communication is connected by toggle switch SW3.
485-
PE
Grounding terminal
PW
External power input terminal for digital input circuits
Voltage range: 1230V
24V
The VFD provides user power; the max. output current is 200mA
S1
Digital input 1
1. Internal impedance: 3.3kΩ
2. Accept 12–30V voltage input
3. This terminal is bi-directional input terminal and supports NPN/PNP
connection modes
4. Max. input frequency: 1kHz
5. All are programmable digital input terminals, users can set the
terminal function via function codes
S2
Digital input 2
S3
Digital input 3
S4
Digital input 4
HDIA
Channels for both high frequency pulse input and S1S4 function inputs