Frequency Inverter ST600 Series High-Performance Multifunction VFD Function parameter list
-143-
P01.28
Time of ending
section of
deceleration S
curve
0.050.0s
0.1s
P01.29
Short-circuit
brake current
When the VFD starts in direct start mode (P01.00=0), set
P01.30 to a non-zero value to enter short-circuit brake.
During stop, if the running frequency of VFD is below the
starting frequency of brake after stop (P01.09), set P01.31
to a non-zero value to enter short-circuit brake after stop,
and then carry out DC brake in the time set by P01.12 (refer
to P01.09P01.12).
Setting range of P01.29: 0.0150.0% (of the rated VFD
output current)
Setting range of P01.30: 0.0–50.0s
Setting range of P01.31: 0.0–50.0s
0.0%
P01.30
Hold time of
short-circuit
brake at startup
0.00s
P01.31
Hold time of
short-circuit
brake at stop
0.00s
P01.32
Pre-exciting time
of jogging
0–10.000s
0.300s
P01.33
Starting
frequency of
braking for
jogging to stop
0–P00.03
0.00Hz
P01.34
Delay to enter
sleep
0–3600.0s
0.0s
P02––Parameters of motor 1
Function
code
Name
Description
Default
value
Modify
P02.00
Type of motor 1
0: Asynchronous motor
1: Synchronous motor
0
P02.01
Rated power of
asynchronous
motor 1
0.13000.0kW
Model-
dependent
P02.02
Rated frequency
of asynchronous
motor 1
0.01HzP00.03 (max. output frequency)
50.00Hz
P02.03
Rated speed of
asynchronous
motor 1
1–60000rpm
Model-
dependent
P02.04
Rated voltage of
asynchronous
motor 1
0–1200V
Model-
dependent
P02.05
Rated current of
asynchronous
motor 1
0.86000.0A
Model-
dependent
P02.06
Stator resistance
0.001–65.535Ω
Model-