Frequency Inverter ST600 Series High-Performance Multifunction VFD Function parameter list
-142-
Sleep
Run
Set frequency curve:
Running frequency curve:
t1 < P01.20, the VFD does not run
t0=P01.34, sleep delay
Run
t2
t1
t0
Frequency lower
limit f0
Frequency f
Time t
Coast to
stop
t1+t2 P01.20, the VFD runs
Setting range: 0.0–3600.0s (valid when the ones place of
P01.19 is 2)
P01.21
Restart after
power cut
This function code sets the automatic running of the VFD at
next power-on after power down.
0: Disabled restart
1: Enable restart, namely the VFD will run automatically
after the time set by P01.22 elapses if the starting
conditions are met.
0
P01.22
Waiting time of
restart after
power cut
This function code sets the waiting time before
automatically running at next power-on after power down.
Output frequency
Running
Power off
Power on
Running
t
t1 t2
t1=P01.22
t2=P01.23
Setting range: 0.0–3600.0s (valid when P01.21 is 1)
1.0s
P01.23
Start delay
This function code sets the delay of the VFD’s wake-up-
from-sleep after running command is given, the VFD will
start to run and output after the time set by P01.23 elapses
to realize brake release.
Setting range: 0.0–600.0s
0.0s
P01.24
Stop speed
delay
0.0600.0s
0.0s
P01.25
Open-loop 0Hz
output selection
0: No voltage output
1: With voltage output
2: Output as per DC brake current of stop
0
P01.26
Deceleration
time of
emergency-stop
0.060.0s
2.0s
P01.27
Time of starting
section of
deceleration S
curve
0.050.0s
0.1s