Frequency Inverter ST600 Series High-Performance Multifunction VFD Installation Guide
-18-
install the VFD on combustible objects like wood).
Away from radioactive substances and combustible objects.
Away from corrosive liquid.
Low salt content.
No direct sunlight.
Altitude
Below 1000m.
If the installation site altitude exceeds 1000m, derate 1% for every increase of
100m; if the installation site altitude exceeds 3000m, consult the local
Sourcetronic seller or office.
Vibration
Up to 5.8m/s
2
(0.6g)
Installation
direction
Install the VFD vertically to ensure good heat dissipation effect.
Note: VFDs must be installed in ventilated environments free of corrosive gases and conductive dust.
4.2.2 Installation direction
The VFD can be installed on the wall or in a cabinet.
The VFD must be installed vertically. Check the installation position according to following
requirements. See Appendix C "Dimension drawings" for detailed outline dimensions.
Figure 4-1 Installation direction of the standard model VFDs
OK
NG
NG
A. Vertical installation
B. Horizontal installation
C. Transverse installation
Figure 4-2 Installation direction of the SP model VFDs
NG
NG
OK
b.Horizontal installation
a. Vertical installation
c.Transverse installation