Frequency Inverter ST600 Series High-Performance Multifunction VFD Function parameter list
-185-
P10––Simple PLC and multi-step speed control
Function
code
Name
Description
Default
value
Modify
P10.00
Simple PLC mode
0: Stop after running once; the VFD stops automatically
after running for one cycle, and it can be started only after
receiving running command.
1: Keep running in the final value after running once; The
VFD keeps the running frequency and direction of the last
section after a single cycle.
2: Cyclic running; the VFD enters the next cycle after
completing one cycle until receiving stop command and
stops.
0
P10.01
Simple PLC
memory selection
0: No memory after power down
1: Memory after power down; PLC memories its running
stage and running frequency before power down.
0
P10.02
Multi-step speed 0
Setting range of the frequency in 0
th
15
th
sections are -
300.0300.0%, 100% corresponds to max. output
frequency P00.03.
Setting range of the running time in 0
th
15
th
sections are
0.06553.5s (min), the time unit is determined by P10.37.
When simple PLC operation is selected, it is required to
set P10.02P10.33 to determine the running frequency
and running time of each section.
Note: The symbol of multi-step speed determines the
running direction of simple PLC, and the negative value
means reverse running.
P10.02
P10.04
P10.06
P10.32
P10.30
P10.28
Deceleration time
(two sections)
Acceleration time
(two sections)
P10.03 P10.05 P10.07 P10.31 P10.33
When selecting multi-step speed running, the multi-step
speed is within the range of -fmaxfmax, and it can be
set continuously. The start/stop of multi-step stop is also
determined by P00.01.
The frequency inverter ST600 high-performance
multifunction VFD can set 16-step speed, which are set
by combined codes of multi-step terminals 1–4 (set by S
terminal, correspond to function code P05.01P05.06)
and correspond to multi-step speed 0 to multi-step speed
15.
0.0%
P10.03
Running time of
step 0
0.0s(min)
P10.04
Multi-step speed 1
0.0%
P10.05
Running time of
step 1
0.0s(min)
P10.06
Multi-step speed 2
0.0%
P10.07
Running time of
step 2
0.0s(min)
P10.08
Multi-step speed 3
0.0%
P10.09
Running time of
step 3
0.0s(min)
P10.10
Multi-step speed 4
0.0%
P10.11
Running time of
step 4
0.0s(min)
P10.12
Multi-step speed 5
0.0%
P10.13
Running time of
step 5
0.0s(min)
P10.14
Multi-step speed 6
0.0%
P10.15
Running time of
step 6
0.0s(min)
P10.16
Multi-step speed 7
0.0%
P10.17
Running time of
0.0s(min)