Frequency Inverter ST600 Series High-Performance Multifunction VFD Function parameter list
-146-
is no need to adjust the protection value during low
speed running.
P02.27
Overload
protection
coefficient of
motor 1
Motor overload multiples M=Iout/(In×K)
In is rated motor current, lout is VFD output current, K is
motor overload protection coefficient.
The smaller the K, the larger the value of M, and the easier
the protection.
When M=116%, protection is performed after motor
overload lasts for 1 hour; when M=150%, protection is
performed after motor overload lasts for 12 minutes; when
M=180%, protection is performed after motor overload
lasts for 5 minutes; when M=200%, protection is
performed after motor overload lasts for 60 seconds; and
when M400%, protection is performed immediately.
1
5
12
60
116%
200%
Time(min)
Motor overload multiple
150% 180%
Setting range: 20.0%–120.0%
100.0%
P02.28
Power display
calibration
coefficient of
motor 1
This function adjusts the power display value of motor 1
only, and it does not affect the control performance of the
VFD.
Setting range: 0.003.00
1.00
P02.29
Parameter
display of motor
1
0: Display as per motor type; under this mode, only
parameters related to current motor type will be displayed.
1: Display all; under this mode, all the motor parameters
will be displayed.
0
P02.30
System inertia of
motor 1
0.000–30.000kgm
2
0.000
kgm
2
P02.31
P02.32
Reserved
/
/
/