Motor overload multiples M=Iout/(In×K)
In is rated motor current, lout is VFD output current, K is
motor overload protection coefficient.
The smaller the K, the larger the value of M, and the easier
the protection.
When M=116%, protection is performed after motor
overload lasts for 1 hour; when M=150%, protection is
performed after motor overload lasts for 12 minutes; when
M=180%, protection is performed after motor overload
lasts for 5 minutes; when M=200%, protection is
performed after motor overload lasts for 60 seconds; and
when M≥400%, protection is performed immediately.
This function adjusts the power display value of motor 1
only, and it does not affect the control performance of the
VFD.
Setting range: 0.00–3.00
0: Display as per motor type; under this mode, only
parameters related to current motor type will be displayed.
1: Display all; under this mode, all the motor parameters
will be displayed.