Frequency Inverter ST600 Series High-Performance Multifunction VFD Function parameter list
-148-
Current loop
proportional
coefficient P
Note:
1. These two parameters are used to adjust PI
parameters of current loop; it affects dynamic response
speed and control precision of the system directly. The
default value needs no adjustment under common
conditions;
2. Fit for SVC mode 0 (P00.00=0) , SVC mode 1
(P00.00=1) and FVC mode (P00.00=3);
Setting range: 0–65535
Current loop
integral coefficient
I
Torque setup
mode selection
0: Keypad (P03.12)
1: Keypad (P03.12)
2: AI1
3: AI2
4: AI3
5: Pulse frequency HDIA
6: Multi-step torque
7: Modbus/Modbus TCP communication
8: PROFIBUS/CANopen/DeviceNet communication
9: Ethernet communication
10: Pulse frequency HDIB
11: EtherCAT/PROFITNET/Ethernet IP communication
12: PLC
Note: For these settings, 100% corresponds to the
motor rated current.
-300.0%–300.0% (rated motor current)
Torque reference
filter time
Source of upper
limit frequency
setup of forward
rotation in torque
control
0: Keypad (P03.16)
1: AI1
2: AI2
3: AI3
4: Pulse frequency HDIA
5: Multi-step
6: Modbus/Modbus TCP communication
7: PROFIBUS/CANopen/DeviceNet communication
8: Ethernet communication
9: Pulse frequency HDIB
10: EtherCAT/PROFITNET/Ethernet IP communication
11: PLC
12: Reserved
Note: For these settings, 100% corresponds to the
max. frequency.
Source of upper
limit frequency
setup of reverse
0: Keypad (P03.17)
1–11: the same as P03.14