Frequency Inverter ST600 Series High-Performance Multifunction VFD Product Overview
-11-
Retension at transient
voltage drop
Keeps running with regenerative energy when the grid
transiently drops.
Supports two groups of motor parameters to control motor
switchover.
Terminal analog input
resolution
Terminal digital input
resolution
2 inputs, AI1: 0–10V/0–20mA; AI2: -10–10V
1 output, AO1: 0–10V /0–20mA
Four regular inputs; max. frequency: 1kHz; internal impedance:
3.3kΩ
Two high-speed inputs; max. frequency: 50kHz; supports
quadrature encoder input; with speed measurement function
One high-speed pulse output; max. frequency: 50kHz
One Y terminal open collector output
Two programmable relay outputs
RO1A NO, RO1B NC, RO1C common port
RO2A NO, RO2B NC, RO2C common port
Contact capacity: 3A/AC250V, 1A/DC30V
Three extension interfaces: SLOT1, SLOT2, SLOT3
Expandable PG card, programmable expansion card,
communication card, I/O card, etc
Support wall-mounting and flange-mounting
Operation ambient
temperature
Ingress protection
rating
Built-in brake units are included in all SP model VFDs.
Conducted emissions of all models meet the requirements of C3
in the IEC/EN 61800-3 standard. The -AS models offers the 30m
motor cable, meeting the C3 requirements.
External filter is optional: Conducted emission can meet the
requirements of C2 in the IEC/EN 61800-3 standard.
Note: It is required to observe the EMC compliance required by
the appendix of the manual. The motor and motor cables shall
be selected based on technical requirements specified in the
appendix of the manual.