Frequency Inverter ST600 Series High-Performance Multifunction VFD Function parameter list
-191-
Note: Speed deviation protection will be invalid if P11.15
is set to 0.0.
Speed
Actual detection
value
Set detection
value
Time t
t1
t2
t2=P11.15
t1<t2, so the VFD continues running
dEu
Running Fault output
Setting range: 0.0–10.0s
P11.16
Automatic
frequency-
reduction during
voltage drop
0–1
0: Invalid
1: Valid
0
P11.17
Proportional
coefficient of
voltage regulator
during
undervoltage stall
0–1000
100
P11.18
Integral coefficient
of voltage regulator
during
undervoltage stall
0–1000
40
P11.19
Proportional
coefficient of
current regulator
during
undervoltage stall
0–1000
25
P11.20
Integral coefficient
of current regulator
during
undervoltage stall
0–2000
150
P11.21
Proportional
coefficient of
voltage regulator
during overvoltage
stall
0–1000
60
P11.22
Integral coefficient
of voltage regulator
during overvoltage
stall
0–1000
10
P11.23
Proportional
coefficient of
current regulator
during overvoltage
0–1000
60