Frequency Inverter ST600 Series High-Performance Multifunction VFD Function parameter list
-196-
motor 2
P12.26
Overload protection
of motor 2
0: No protection
1: Common motor (with low-speed compensation)
2: Frequency-variable motor (without low-speed
compensation)
2
P12.27
Overload protection
coefficient of motor 2
Motor overload multiples M = Iout/(In×K)
In is rated motor current, lout is VFD output current, K is
motor overload protection coefficient.
The smaller the K, the larger the value of M, the easier
the protection.
M=116%: Protection will be applied when the motor
overloads for 1h;
M=150%: Protection will be applied when the motor
overloads for 12min;
M=180%: Protection will be applied when the motor
overloads for 5min;
M>=400%: Protection will be applied immediately.
1
5
12
60
116%
200%
Time(min)
Motor overload multiple
150% 180%
Setting range: 20.0%–120.0%
100.0%
P12.28
Power display
calibration coefficient
of motor 2
0.003.00
1.00
P12.29
Parameter display of
motor 2
0: Display based on the motor type; under this mode,
only parameters related to current motor type will be
displayed.
1: Display all; under this mode, all the parameters will
be displayed.
0
P12.30
System inertia of
motor 2
0–30.000kgm
2
0.000
kgm
2
P12.31
P12.32
Reserved
/
/
/