Frequency Inverter ST600 Series High-Performance Multifunction VFD Function parameter list
-199-
0: No parity check (N, 8, 1) for RTU
1: Even parity (E, 8, 1) for RTU
2: Odd parity (O, 8, 1) for RTU
3: No parity check (N, 8, 2) for RTU
4: Even parity (E, 8, 2) for RTU
5: Odd parity (O, 8, 2) for RTU
P14.03
Communication
response delay
0–200ms
It refers to the time interval from when the data is
received by the VFD to the moment when the data is sent
to the controlling computer. If the response delay is less
than the system processing time, the response delay will
be subject to system processing time; if the response
delay is longer than the system processing time, data will
be sent to the controlling computer at a delay after data
process is done by system.
5ms
P14.04
RS485
Communication
timeout period
0.0 (invalid) –60.0s
This parameter will be invalid if it is set to 0.0;
When it is set to a non-zero value, if the time interval
between current communication and the next
communication exceeds the communication timeout
period, the system will report "Modbus/Modbus TCP
communication fault" (CE).
Under common situations, it is set to 0.0. In systems
which have continuous communication, users can
monitor the communication condition by setting this
parameter.
0.0s
P14.05
Transmission error
processing
0: Alarm and coast to stop
1: Do not alarm and continue running
2: Do not alarm and stop as per the stop mode
(under communication control mode only)
3: Do not alarm and stop as per the stop mode
(under all control modes)
0
P14.06
Communication
processing action
0x000–0x111
Ones:
0: Write operation has response
1: Write operation has no response
Tens:
0: Communication password protection is invalid
1: Communication password protection is valid
Hundreds place: Valid only for RS485 communication
0: User-defined addresses specified by P14.07 and
P14.08 are invalid
1: User-defined addresses specified by P14.07 and
P14.08 are valid
0x000
P14.07
User-defined
running command
0x00000xFFFF
0x2000