Frequency Inverter ST600 Series High-Performance Multifunction VFD Troubleshooting
-258-
[60] Failed to identify the
expansion card in card
slot 1
There is data transmission in
interfaces of card slot 1, however,
it cannot read the card type
Confirm whether the
expansion card inserted can
be supported;
Stabilize the expansion card
interfaces after power down,
and confirm whether fault still
occurs at next power-on;
Check whether the insertion
port is damaged, if yes,
replace the insertion port after
power down
[61] Failed to identify the
expansion card in card
slot 2
There is data transmission in
interfaces of card slot 2, however,
it cannot read the card type
Confirm whether the
expansion card inserted can
be supported;
Stabilize the expansion card
interfaces after power down,
and confirm whether fault still
occurs at next power-on;
Check whether the insertion
port is damaged, if yes,
replace the insertion port after
power down
[62] Failed to identify the
expansion card in card
slot 3
There is data transmission in
interfaces of card slot 3, however,
it cannot read the card type
Confirm whether the
expansion card inserted can
be supported;
Stabilize the expansion card
interfaces after power down,
and confirm whether fault still
occurs at next power-on;
Check whether the insertion
port is damaged, if yes,
replace the insertion port after
power down
[63] Communication
timeout occurred to the
expansion card in card
slot 1
There is no data transmission in
interfaces of card slot 1
Confirm whether the
expansion card inserted can
be supported; stabilize the
expansion card interfaces
after power down, and confirm
whether fault still occurs at
next power-on; check whether
the insertion port is damaged,
if yes, replace the insertion
port after power down
[64] Communication
timeout occurred to the
expansion card in card
slot 2
There is no data transmission in
interfaces of card slot 2
Confirm whether the
expansion card inserted can
be supported;
Stabilize the expansion card