Frequency Inverter ST600 Series High-Performance Multifunction VFD Basic Operation Instructions
-79-
P02.09
Mutual inductance of
asynchronous motor 1
0.1–6553.5mH
Model-
dependent
P02.10
No-load current of
asynchronous motor 1
0.1–6553.5A
Model-
dependent
P02.15
Rated power of synchronous
motor 1
0.1–3000.0kW
Model-
dependent
P02.16
Rated frequency of
synchronous motor 1
0.01Hz–P00.03 (max. output frequency)
50.00Hz
P02.17
Number of pole pairs of
synchronous motor 1
1–50
2
P02.18
Rated voltage of synchronous
motor 1
0–1200V
Model-
dependent
P02.19
Rated current of synchronous
motor 1
0.8–6000.0A
Model-
dependent
P02.20
Stator resistance of
synchronous motor 1
0.001–65.535Ω
Model-
dependent
P02.21
Direct-axis inductance of
synchronous motor 1
0.01–655.35mH
Model-
dependent
P02.22
Quadrature-axis inductance of
synchronous motor 1
0.01–655.35mH
Model-
dependent
P02.23
Counter-emf constant of
synchronous motor 1
0–10000
300
P05.01–
P05.06
Function of multi-function
digital input terminal (S1S4,
HDIA, HDIB)
35: Motor 1 switches to motor 2
/
P08.31
Switching between motor 1
and motor 2
0x00–0x14
Ones: Switch-over channel
0: Switch over by terminal
1: Switch over by Modbus/Modbus TCP
communication
2: Switch over by
PROFIBUS/CANopen/DeviceNet
3: Switch over by Ethernet communication
4: Switch over by
EtherCAT/PROFITNET/Ethernet IP
communication
Tens: Motor switch-over during running
0: Disable switch-over during running
1: Enable switch-over during running
00
P12.00
Type of motor 2
0: Asynchronous motor
1: Synchronous motor
0