SUNFAR C300 41
C300 series of non-sensor current vector-control inverter manual
This parameter will valid only when F0.4 is set as ###1
It is used for selecting operation channel of inverter and function of key
The first part of LED (form right to left): to select operation channel of inverter.
0: Panel control
The inverter is controlled by key on the panel. And external control terminal,
FWD state will affect output phase sequence of inverter. When FWD is on,
connecting with GND, output phase sequence will reverse with setting sequence,
on the contrary, output phase sequence will go the same way with setting
sequence.
1: External terminals control
The inverter receives running instruction form the situation of being on or off of
external terminals FWD、REV and GND, while the mode is decided by parameter
[F0.5]. The manufacture setting is shown as follows:
2:Serial Communication RS485 interface
The inverter will receive running instruction from the PC or Master.
The second part of LED (form right to left): to select function of the key
0: It is valid for panel.
When F0.4 is 0000, key on the operation panel is available.
1: It is valid for all kinds of control method.
When F0.4 is not 0 and pressing key, inverter will stop urgently and twinkle
display Fu.16.
The third and fourth part of LED(form right to left):Reserved.
It is used for setting control modes of external terminals.
0:Two-line mode 1
(Manufacture Setting)
Instruction Stop instruction FWD instruction REV instruction
Ter minal s
State
FWD
REV
GND
FWD
REV
GND
FWD
REV
GND
FWD
REV
CM
F0.5 Combination methods of instruction terminals Setting range:0 ~ 2