Swegon reserves the right to alter specications. 20220323
66
WISE User Manual
Communication to the shunt group
The calculated demand for each function group can be read
from SuperWISE to be used by a shunt group controller to deliver
the most optimal temperature possible to the each function
group.
If a shunt group controller from Swegon is used, SuperWISE
will send the setpoint for each function group to the appro-
priate shunt group via Modbus TCP/IP. For this to work, the IP
address of each shunt group is linked to the correct function
group, which is done by Swegon’s technicians. In addition to
the temperature setpoint, SuperWISE sends information about
possible cooling and heating needs, which allows the shunt
group controller to switch o the pump if the function group
does not have a need.
If a shunt group controller from another supplier is used, the
temperature setpoints calculated by SuperWISE can be made
available via Modbus /BACnet to the master system.
Communication to the cooling/heating
producer
The communication between SuperWISE and the cooling/heat-
ing producer from BlueBox is performed via ModBus TCP/IP. The
communication is activated by Swegon’s technicians and then
happens automatically.
Combine with SMARTLink+
When a BlueBox liquid chiller or heat pump is used in a system
together with SuperWISE and the SMARTLink+ function, the
SuperWISE calculated requirements of cooling media (for circuits
A and B) and the calculated requirements of heating media (for
circuits A and B) as consumers of cooling or heating are linked
in SMARTLink+. The liquid chiller/heat pump takes into account
all connected heating and/or cooling consumers, e.g. two air
handling units and a WISE system, and optimises the production
of cooling and/or heating to satisfy the needs of the consumer
with the highest demand.
Up to two liquid chillers and two heat pumps can be intercon-
nected in the BlueBox control unit. Multilogic or Hyzer increases
the number of producers that can be connected to a total of 32.
These in turn can handle up to ten consumers (SuperWISE or air
handling units).
Combine water optimization with SMARTLink+ for optimal energy
performance. Water optimization functions, air optimization
functions and SMARTLink+ can be used independently or combined.
If a cooling/heating producer from another supplier is used, the
temperature setpoints and the need of cooling and/or heating
calculated by SuperWISE can be made available via Modbus/
BACnet to the master system.
WISE
WISE Air Optimization
WISE Water
Optimization
C&H production
SMARTLink +
What components are used?
System accessories
Shunt group controller from
Swegon