SECTION VII - SUPERVISOR KEY ACCESS
54
CONFIG > TESTS > PROKEE® > FIELDS
Display the contents of a ProKee® once descriptive field at a time. The
specific fields displayed are dependent on the type of ProKee®
inserted.
CONFIG > TESTS > PROKEE® > ASCII
Displays the contents of a Prokee® in ASCII, both byte position and
value are displayed.
CONFIG > TESTS > PROKEE® > HEX
Displays the contents of a Prokee® in HEX, both byte position and
value are displayed.
CONFIG > TESTS > PROKEE® > PIN
Displays the PIN of a Prokee®.
CONFIG > TESTS > COUNT
The count test provides a way to both determine the pulser divide rate and
troubleshoot for pulser failure.
The 0 indicators correspond with the location on the pedestal I/O board
where the pulsers are wired. To perform the count test follow these steps:
Before switching to the count screen, note that the manual mode
switches are in auto.
1) Once at the count test screen, place the manual mode switches in
manual.
2) Turn on the pump handle and dispense product. The 0 indicator counts
right along with the dispenser meter. By pumping one gallon on the
dispenser, the counter on the FMU screen shows how many pulses equal
one gallon. (The count may show one pulse either way and is still
considered accurate.)
CONFIG > TESTS > RESET
Opting to perform this test will trigger the FMU to power fail and
immediately power up thereby testing the integrity of the FMU’s internal
hardware and recognition of any peripheral devices connected to the
FMU.