EasyManua.ls Logo

TAC 2413 - Page 36

TAC 2413
70 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7:4 (24), 0-004-7614-0 (GB) TAC AB, 1998-10-23
TAC 2413 Handbook Functional description
The heat recovery is controlled to 100 % when FF starts, and the posi-
tion of the heating valve is determined by the outdoor temperature. It
is completely closed at outdoor temperatures 10 °C, and opens on a
linear basis without breakpoints with decreasing outdoor temperatures.
The slope of the curve is defined at –10 °C and is factory set to 50 %. If
no outdoor sensor has been installed, the slope is equal to that at –10 °C.
During electric heating, the same time delay applies between the fans,
but the control signal to the electric battery is 0% until TF starts. The
control sequence is started together with TF.
P No. Parameter Min Max Factory set. Change Comment
P 32 Delay, start TF at 5 sec 300 sec 5 sec
+10 °C
P 33 Delay, start TF at 5 sec 300 sec 60 sec
–10 °C
P 12 Weekly program 1/2 speed 07-17 Mon-Fri, one speed op.
P 13 Weekly program 1/1 speed
P 14 Timer 0 min 300 min 120 min Extended operation
P 90 Outd. temp. block 1/1 speed –50°C 20°C –50°C
Status
The display shows the functions that are activated using the P No.
When an output signal is active for the AHU, its symbol is dis-
played. The following symbols are found on the display:
!
: Alarm : Manual
operation
+
: Heating coil
1
2
: Half speed, one
sp.
: Cooling coil
1
1
: Full speed
+
: Heat recovery : Off
: Electric heating : Timed operation
FF : Return air fan D
X
: DX cooling
TF : Supply air fan P
K
: Pump, cooling
coil
P
V
: Pump, heating
coil

Related product manuals