TAC 2413 Handbook Troubleshooting
6 Troubleshooting
TAC 2413 is normally a very reliable controller. If there should
be any problem in spite of this, you may use the following tips for
troubleshooting. If you need further help, please contact your ne-
arest TAC service office.
Problem Check that...
The window is empty the controller has power
An alarm has stopped the the alarm has been acknowledged
AHU or reset, please refer to the
section Alarms in Chapter 7
The temperature in the the AHU is in timed operation and
ventilating system is too low that a holiday program is not
active
an alarm has not stopped
the AHU
high current protectors and
power switches are on
the pump for the heating coil
is running
the plumbing system is not full
of air and the pressure is normal
the main pump is running
the heating source (district
heating or boiler) has the
correct temperature
heat recovery provides the
normal rise in temperature
the cooling coil is not
engaged