EasyManua.ls Logo

TAC 2413 - Outdoor Compensation

TAC 2413
70 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7:6 (24), 0-004-7614-0 (GB) TAC AB, 1998-10-23
TAC 2413 Handbook Functional description
P No. Parameter Min Max Factory set. Change Comment
P 02 Supply air temp. setpoint Calculated
P 04 Room/exhaust air temp. SP Calculated
P 10 Heating setpoint 0 °C 50 °C 20 °C
P 11 Cooling setpoint 0 °C 50 °C 22 °C
P 26 Min. SP supply air, heating 0 °C 50 °C 14 °C
P 27 Min. SP supply air, cooling 0 °C 50 °C 12 °C
P 28 Max. setpoint supply air 0 °C 50 °C 35 °C
P 70 Gain, room controller 1 20 2
P 71 I time, room controller 1min 60 min 20 min
P 89 Room sensor adjustment –5 °C 5 °C 0 °C °C/°C
P 92 Dead zone, supply air c. 5 20 5 ×0,1 (5=0,5°C)
7.3.3 Outdoor compensation
If no outdoor sensor is installed, this function will not be available,
and the P No. is not shown. The supply air or room temperature set-
point can be compensated directly by the outdoor temperature. The
compensation, which may be positive or negative, states in °C how
much the supply air or room/return air temperature setpoint is to be
shifted.
There are two curves, one for the summer and one for the winter com-
pensation, see the figure below.
The outdoor compensation is not active on delivery. It is activated by
setting the desired compensation values in the list, P 50 for winter
compensation and P 53 for summer compensation.
The summer compensation starts when the outdoor temperature is
greater than “Start summer compensation”. The maximum com-
pensation is achieved when the outdoor temperature is greater
than or equal to “Stop summer compensation”.
8
0
–20
–10
10
20 30
40
6
4
2
Max w.comp.
Max s.comp.
Outdoor temp.
(°C)
Start
w.comp.
Start
s.comp.
Stop
s.comp.
Stopp
w.comp.
Compensation °C

Related product manuals