7:18 (24), 0-004-7614-0 (GB) TAC AB, 1998-10-23
TAC 2413 Handbook Functional description
7.4 Clock
The controller contains a calendar clock which switches to and from
summer time automatically, as well as compensating for leap years.
The clock must be set manually after a power failure which lasts for
longer than 48 hours.
P No. Parameter Min. Max. Factory set. Change Comment
P 96 Clock 00:00
P 97 Date 01.01
P 99 Year 1998
7.4.1 Summer time
The automatic switch to/from summer time may be omitted by set-
ting parameter P 46, “Choice of summer time”.
P No. Parameter Min. Max. Factory set. Change Comment
P 46 Choice of summer time 1 0=ej aktiv, 1=mars till okt
7.4.2 Summer period
Some functions depend on whether TAC 2413 is set for the summer
period or winter period. The cooling control is only allowed to apply,
and the pump for the heating coil is only allowed to stop, during the
summer period.
The parameter list contains adjustable “start months” for the summer
and winter periods, respectively. The period is started on the first day
of the set “start month”.
If the cooling demand applies all year round, set the parameters as
follows: P 47=1 and P 48=13.
P No. Parameter Min. Max. Factory set. Change Comment
P 47 Start month of 1 12 5
summer period
P 48 Start month of 1 13 10
winter period