To Previous Page IconTo Previous Page
Loading...
8
Example of connection between the 7200MA and typical peripheral devices are
shown as below.
Induction
motor
Power supply
Power supply
switch(NFB)
and earth
leakage
breaker
Electromagnetic
contactor
AC reactor
Input noise
filter
7200MA
inverter
Zero phase
core
Power supply switch(NFB) and earth leakage breaker
Choose the
p
ower su
pp
l
y
switch
(
NFB
)
of
p
ro
p
er current
rating.
Do not use the
p
ower su
pp
l
y
switch
(
NFB
)
as the switch
that the inverter is used to control the runnin
g
or sto
p
o
f
motor.
When the earth leaka
g
e breaker installed to
p
rotect the
leaka
g
e current fault, be sure that the earth leaka
g
e breaker
has the sensitivit
y
am
p
era
g
e
200mA
p
er inverter and
operation time 0.1 sec to avoid false-triggering.
Electromagnetic contactor
In normal o
p
eration,
y
ou don’t need an electroma
g
netic
contactor. However, you need to install an electro-
ma
g
netic contactor while in the case of se
q
uence control
throu
g
h the external device or automaticall
y
re-start after
power outage.
Do not use the electroma
g
netic contactor as the switch that
control the operation of running or stop.
AC reactor
The AC-side reactor on the in
p
ut AC side can im
p
rove the
power factor and suppress the surge current.
Input noise filter
7200MA will com
p
l
y
with the EN55011 class A re
g
ulation i
f
an input noise filter (specified by TECO) is used.
Please refer to the selection
g
uide “1.9 Peri
p
heral device”
on page 24.
7200MA inverter
In
p
ut
p
ower su
pp
l
y
can be connected to an
y
terminal
R/L1, S/L2, T/L3 on the terminal block. The
p
hase
se
q
uence of in
p
ut
p
ower su
pp
l
y
is irrelevant to
p
hase
sequence.
Please connect the
g
round terminal E to the site
g
round
securely.
Zero phase core
Install the zero
p
hase corer to eliminate noise transmitted
between the power line and the inverter.
Please refer to the selection
g
uide “1.9 Peri
p
heral device”
on page 25
.
Induction Motor
If one inverter is to drive more than one motors, the
inverter’s rated current should be much
g
reater than the
sum of total current of motors while in operation.
The inverter and the motor should connect to the
g
round
separately.