23
■ AC reactor
• An AC reactor can be added on the power supply side if the inverter is
connected to a much larger capacity power supply system, or the inverter is
within short distance (<10m) from power supply systems, or to increase the
power factor on the power supply side.
• Choose the proper AC reactor according to the below list.
Table 5 AC reactor list
Inverter Model AC reactor
VHP
Rated
current
Code No.
Specification
(mH/A)
1 4.8A 3M200D1610021 2.1mH/5A
2 6.5A 3M200D1610030 1.1mH/10A
220V
1
φ
/3
φ
3 9.6A 3M200D1610048 0.71mH/15A
5.4 17.5A 3M200D1610056 0.53mH/20A
7.5 24A 3M200D1610064 0.35mH/30A
10 32A 3M200D1610072 0.265mH/40A
15 48A 3M200D1610081 0.18mH/60A
220V
3
φ
20 64A 3M200D1610099 0.13mH/80A
1 2.6A 3M200D1610137 8.4mH/3A
2 4A 3M200D1610145 4.2mH/5A
3 4.8A 3M200D1610153 3.6mH/7.5A
5.4 8.7A 3M200D1610161 2.2mH/10A
7.5 12A 3M200D1610170 1.42mH/15A
10 15A 3M200D1610188 1.06mH/20A
15 24A 3M200D1610196 0.7mH/30A
440V
3
φ
20 32A 3M200D1610200 0.53mH/40A
Note: The AC reactors are applied only to input side. Do not apply it to output side.