40
(12) Monitor 1 (Bn-12)
(13) Monitor 2 (Bn-13)
In the DRIVE mode, 2 inverter input/output statuses can be monitored at the same
time. The specified items can be set through the setting of Bn-12 and Bn-13. For
more details, refer to Table 8.
Example:
(1) Bn-12= 02
Bn-13= 01
Display O/P Freq. 15.00Hz
Freq.Cmd. 15.00Hz
(2) Bn-12= 03
Bn-13= 05
Display O/P I 21.0A
DC Volt 311V
(3) Bn-12= 11
Bn-13= 12
Display I/P Term. 00101010
O/P Term. 00010010
Note : While monitoring, use the or key to show the next lower-row
displayed. But the setting of Bn-12 and Bn-13 does not change.
Table 8
Setting
Monitoring
contents
Setting
Monitoring
contents
Bn-12= 01 Freq.Cmd. Bn-13= 01 Freq.Cmd.
Bn-12= 02 O/P Freq. Bn-13= 02 O/P Freq.
Bn-12= 03 O/P I Bn-13= 03 O/P I
Bn-12= 04 O/P V Bn-13= 04 O/P V
Bn-12= 05 DC Volt Bn-13= 05 DC Volt
Bn-12= 06 Term. VIN Bn-13= 06 Term. VIN
Bn-12= 07 Term. AIN Bn-13= 07 Term. AIN
Bn-12= 08 Term. AUX Bn-13= 08 Term. AUX
Bn-12= 09 ~ Output(AO1) Bn-13= 09 ~ Output(AO1)
Bn-12= 10 ~ Output(AO2) Bn-13= 10 ~ Output(AO1)
Bn-12= 11 I/P Term Bn-13= 11 I/P Term
Bn-12= 12 O/P Term Bn-13= 12 O/P Term
Bn-12= 13 Sp. FBK Bn-13= 13 Sp. FBK
Bn-12= 14 Sp. Compen. Bn-13= 14 Sp. Compen.
Bn-12= 15 PID I/P Bn-13= 15 PID I/P
Bn-12= 16 PID O/P(Un-16) Bn-13= 16 PID O/P(Un-16)
Bn-12= 17 PID O/P(Un-17) Bn-13= 17 PID O/P(Un-17)
Bn-12= 18 Motor Sp. Bn-13= 18 Motor Sp.