(44) Auto_Run Mode Selection (Sn-44)
(45) Auto_Run Mode Setting Selection (Sn-45~Sn-60)
•A PLC operation mode is ready to use with the following setting of the multi-step
frequency command1~16 (An-01~An-16), Auto_Run mode time setting (Bn-
21~Bn-36) under the auto_run mode selection (Sn-44). The FWD/REV direction
can be set with the setting of Sn45~60.
•In the auto_Run mode, the multi-step frequency command 1∼4 derived from the
multi-function input terminals g~j are ineffective.
•Some example in auto_run mode:
(A)Single Cycle Running (Sn-44= 1, 4)
The inverter will run for a single full cycle based upon the specified setting
mode. Then, it will stop.
For example :
Sn-44=1 Sn-45~47=1
(FWD)
Sn-48=2
(REV)
Sn-49~60=0
An-01=15Hz An-02=30Hz An-03=50Hz An-04=20Hz
Bn-21=20s Bn-22=25s Bn-23=30s Bn-24=40s
An-05~16=0Hz Bn-25~36=0s
15 Hz
30 Hz
50 Hz
Freq.
20 Hz
An-01
An-02
An-03
An-04
20s
25s 30s 40s
(Bn-21)
(Bn-22) (Bn-23) (Bn-24)
(B) Periodic Running (Sn-44=2, 5)
The inverter will repeat the same cycle periodically.
For example :
Sn-44 = 2
An-01∼16, Bn-21∼36, Sn-45-60 : same setting as the example (A)
15 Hz
30 Hz
50 Hz
Freq.
20 Hz
An-01
An-02
An-03
An-04
20s 25s 30s 40s
(Bn-21)
(Bn-22) (Bn-23)
(Bn-24)
20s
(Bn-21)
An-01
An-02
An-03
An-04
25s
30s
40s
(Bn-22)
(Bn-23)
(Bn-24)