87
(29)Multi-Function Analog Input Function Selection (Sn-29)
•The settings and functions for the multi-function analog input (terminal AUX) are
listed in Table 15.
Table 15 Multi-function analog input function list
Setting
Function LCD Display Description (100% output corresponds to 10 V level)
00
Auxiliary frequency command Auxilary Freq.Cmd.
(Max. output frequency)
01
Frequency command
gain (FGAIN)
∼Freq. Cmd.Gain
Total gain= Bn-05 ×FGAIN
(Frequency command in voltage form, terminal VIN
frequency command)
02
Frequency command
bias 1
(FBIAS1)
Cmd. Bias 1
Total bias= Bn-06 + FBIAS1
03
Frequency command
bias 2
(FBIAS2)
Cmd. Bias 2
Total bias= Bn-06 + FBIAS2
04
Overtorque
detection level
Over Tq. Level
According to analog input voltage (0∼10V), change
overtorque detection level (setting of Cn-32 is disabled)
05
Output frequency bias (VBIAS)
Output Voltage
Total output voltage= V/F pattern voltage + VBIAS
06
Scaling of ACC/DEC time(TK)
Acc&Dec Coeff
Real ACC/DEC time= ACC/DEC time (Bn-0~24) / TK
07
DC injection braking DC Brakin current
According to analog input voltage (0∼10V), change
the level of DC injection current (0-100%).
(inverter rated current=100%, the setting of DC
injection current Cn-15 is disabled )
08
Stall prevention level
during running
Run Still Level
According to analog input voltage (1.5V∼10V), change
the level of stall prevention during running (30%∼200%)
(inverter rated current=100%, the setting Cn-26 is disabled.)
09
PID control reference
input
PID Command
Multi-function analog input (terminal AUX) used as
PID control reference input (0~10V). Please refer to
“PID CONTROL BLOCK DIAGRAM” on page 42.
10
Frequency command
lower limit
Freq. Cmd. Low Bound
Change the frequency command lower-limit (0-100%)
value according to the then analog input voltage (0~10V)
(Max. output frequency (Cn-02) corresponds to the
100% analog output. The actual lower-limit is
determined by the maximum of Cn-19 and the value
corresponding to the multi-function analog input
terminal).
11
Jump frequency setting4 Freq Jump 4
Set the jump frequency 4, according to analog input
voltage (0~10V),
while Cn-20~Cn-23 can be used to set
the jump frequency 1~3 and their jump frequency width.
12
RS-485 communication
application
Comm. Control
The analog value of AUX (0-1024/0-10V) can be read
through RS-485 communication.