90
•During Running (Setting:00)
OFF Run source OFF, inverter is off.
ON Run source ON, or Run source OFF but residues output exists
•Zero Speed (Setting:01)
OFF Output frequency
≧
MIN. output frequency (Cn-07)
ON Output frequency
<
MIN. output frequency (Cn-07)
•Frequency Agree : (Setting:02)
•Setting Frequency Agree : (Setting:03)
•Output Frequency Detected 1 : (Setting:04)
•Output Frequency Detected 2 : (Setting:05)
•Refer frequency detection function on page 55.
•Inverter Ready (Setting:06)
•Undervoltage Detected (Setting:07)
• When the DC link voltage of main circuit is lower than the
UNDERVOLTAGE
DETECTION LEVEL
(Cn-39), the output contact is in ‘ON’ state.
•Output Blocked (Setting:08)
•Run Command Mode (Setting:09)
OFF
Remote Mode
Sn-04 = 1,2, or multi-function in
ut terminal
g~j
is set as Local/remote control I
mode or Local/remote control II mode and contact terminal is OFF
. Remote-SEQ LED
is light in LCD digital operator
ON
Local Mode
Sn-04 = 0 multi-function in
ut terminal
g~j
is set as Local/remote control I mode
and contact terminal is ON
.Remote-SEQ LCD is OFF, run command is from LCD
digital operator
•Frequency Command Mode (Setting:10)
OFF
Remote mode
Sn-05 = 1,2
,
or multi- function in
ut terminal
g~j
is set as Local/remote control I
mode or Local/remote control II mode and contact terminal is OFF
. Remote-REF LED
is light in LCD digital operator
ON
Local mode
Sn-05 = 0 multi- function in
ut terminal
g~j
is set as Local/remote control I mode
and contact terminal is ON
. Remote-REF LED is OFF, run command is from LCD
digital operator