90
During Running (Setting:00)
OFF Run source OFF, inverter is off.
ON Run source ON, or Run source OFF but residues output exists
Zero Speed (Setting01)
OFF Output frequency
MIN. output frequency (Cn-07)
ON Output frequency
MIN. output frequency (Cn-07)
Frequency Agree : (Setting02)
Setting Frequency Agree : (Setting03)
Output Frequency Detected 1 : (Setting04)
Output Frequency Detected 2 : (Setting05)
Refer frequency detection function on page 55.
Inverter Ready (Setting06)
Undervoltage Detected (Setting07)
When the DC link voltage of main circuit is lower than the
UNDERVOLTAGE
DETECTION LEVEL
(Cn-39), the output contact is in ‘ON’ state.
Output Blocked (Setting08)
Run Command Mode (Setting09)
OFF
Remote Mode
(
Sn-04 = 1,2, or multi-function in
p
ut terminal
g~j
is set as Local/remote control I
mode or Local/remote control II mode and contact terminal is OFF
)
. Remote-SEQ LED
is light in LCD digital operator
ON
Local Mode
(
Sn-04 = 0 multi-function in
p
ut terminal
g~j
is set as Local/remote control I mode
and contact terminal is ON
)
.Remote-SEQ LCD is OFF, run command is from LCD
digital operator
Frequency Command Mode (Setting10)
OFF
Remote mode
(
Sn-05 = 1,2
or multi- function in
p
ut terminal
g~j
is set as Local/remote control I
mode or Local/remote control II mode and contact terminal is OFF
)
. Remote-REF LED
is light in LCD digital operator
ON
Local mode
(
Sn-05 = 0 multi- function in
p
ut terminal
g~j
is set as Local/remote control I mode
and contact terminal is ON
)
. Remote-REF LED is OFF, run command is from LCD
digital operator