62
3.4 System Parameters Sn-□□
Function
Parameter
No.
Name
LCD display
(English)
Description
Factory
Setting
Ref.
Page
Ca
p
acit
y
Settin
g
Sn-01
Inverter Ca
p
acit
y
Selection
Sn-01= 01
220V 1HP
Inverter capacity selection
*1 69
V/F
Curve
Sn-02
V/F Curve
Selection
Sn-02= 01
V/F curve
0~14 : 15 fixed V/F curve pattern
15 : arbitrary V/F pattern selection
70
O
p
erator
Status
Sn-03 O
p
erator Dis
p
la
y
Sn-03= 00
Setting Valid
0 :
An-□□, Bn-□□, Cn-□□, Sn-□□
setting & reading enabled
1 : An-□□, settin
g
& readin
g
enabled
Bn-□□,Cn-□□,Sn-□□ reading
only
2~5 : reserved
6 : clear fault message
7 : 2-wire initialization (220V/440V)
8 : 3-wire initialization (220V/440V)
9 : 2-wire initialization (200V/415V)
10 : 3-wire initialization (200V/415V)
11 : 2-wire initialization (200V/380V)
12 : 3-wire initialization (200V/380V)
13~15 : reserved
73
Sn-04
Run Source
Selection
Sn-04= 0
Run source O
p
erator
Run source
0 : Operator
1 : Control terminal
2 : RS-485 communication
073
Sn-05
Frequency
Command
Selection
Sn-05= 0
Ref. Cmd. O
p
erator
Frequency Command
0 : Operator
1 : Control circuit terminal
2 : RS-485 communication
073
Sn-06
Stopping
Method
Selection
Sn-06= 0
Dec. Stop
0 : Deceleration to Stop
1 : Coast to Stop
2 : Whole_range braking stop
3 : Coast to Stop with Timer
(restart after time Bn-02)
073
Sn-07
Priority of
Stopping
Sn-07= 0
Stop Key Valid
If operation command from control ter-
minal or RS-485 communication port
0 : operator stop key effective
1 : operator stop key not effective
075
Sn-08
Prohibition of
REV Run
Sn-08= 0
Allow Reverse
0 : reverse run enabled
1 : reverse run disabled
075
Sn-09
Output
Frequency
Up/Down
Function
Sn-09= 0
Inhibit UP/DOWN
0
:
Reference fre
q
uenc
y
is chan
g
ed
throu
g
h the ke
y
”UP/DOWN”
p
ressin
g
,
later followed b
y
ke
y
“EDIT/ENTER”
p
ressin
g
, and then this out
p
ut fre
q
.
will be acknowledged.
1 : reference frequency will be
acknowledged immediately after the
key ”UP/DOWN” pressing.
075
O
p
eration
Control
Mode
Selection
Sn-10
Frequency
Command
Characteristics
Selection
Sn-10= 0
Ref. Cmd. Fwd. Char.
0 : Reference command has forward
characteristics
(0~10V or 4~20mA/0~100%
1 : Reference command has reverse
characteristics
(10~0V or 20~4mA/0~100%)
076

Table of Contents