EasyManua.ls Logo

TECO speecon 7200ma - Main Circuit Wiring; Wire Size and Connector Selection

TECO speecon 7200ma
128 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
15
1.6 Wiring main circuit and notice
Main circuit wiring
The non-fusible-breaker (NFB) should be installed between the AC source and
the R/L1-S/L2-T/L3 input terminal of 7200MA inverter. The user can make his own
decision of installing electromagnetic contactor block (MCB) or not. To protect
against the false triggering of leakage-current, the user should install a leakage
current breaker with amperage sensitivity200mA and operation time0.1 sec.
Table 3 220V and 440V class applicable wire size and connector
7200MA model Wire size (mm
2
)
Power
supply
Applicable
Power Rating
(HP)
*1
Rated
KVA
Rated
current
(A)
Main
circuit
*2
Ground
connection
wire E (G)
Control
wire
*3
NFB
*4
MCB
*4
1HP 2 4.8 25.5 25.5 0.52 TO-50EC(15A) CN-11
2HP 2.7 6.4 25.5 3.55.5 0.52 TO-50EC(20A) CN-11
220V
1
φ
3
φ
3HP 4 9.6 3.55.5 3.55.5 0.52 TO-50EC(20A) CN-11
5.4HP 7.5 17.5 5.5 5.5 0.52 TO-50EC(30A) CN-16
7.5HP 10.1 24 8 5.580.52 TO-100S(50A) CN-18
10HP 13.7 32 8 5.580.52 TO-100S(60A) CN-25
15HP 20.6 48 22 8 0.52
TO-100S(100A)
CN-50
220V
3
φ
20HP 27.4 64 30 8 0.52
TO-100S(100A)
CN-65
1HP 2.2 2.6 25.5 25.5 0.52 TO-50EC(15A) CN-11
2HP 3.4 4 25.5 3.55.5 0.52 TO-50EC(15A) CN-11
3HP 4.1 4.8 25.5 3.55.5 0.52 TO-50EC(15A) CN-11
5.4HP 7.5 8.7 25.5 3.55.5 0.52 TO-50EC(15A) CN-18
7.5HP 10.3 12 35.5 3.55.5 0.52 TO-50EC(20A) CN-18
10HP 12.3 15 5.5 5.5 0.52 TO-50EC(30A) CN-25
15HP 20.6 24 814 8 0.52 TO-50EC(30A) CN-25
440V
3
φ
20HP 27.4 32 814 8 0.52 TO-100S(50A) CN-35
*1 : It is assumed constant torque load.
*2 : The main circuit has terminals of R/L1, S/L2, T/L3, U/T1, V/T2, W/T3, B1/P,
B2/R, B2,Θ.
*3 : The control wire is the wire led to the pin terminals of control board.
*4 : In Table 3, the specified Part No. of NFB and MC are the item No. of the
products of Taian. The customer can use the same rating of similar products
from other sources. To decrease the noise interference, be sure to add R-C
surge suppressor (R: 10/5W, C: 0.1µF/1000VDC) at the 2 terminals of coils
of electromagnetic contactor.

Table of Contents

Related product manuals