(3) Operator Display (Sn-03)
Parameter code (Sn-03= 0 or 1)
Set the parameter Sn-03 as 0 or 1 to determine the access status as follows.
DRIVE mode PRGM mode
Sn-03
Set Read Only Set Read Only
0 An, Bn Sn, Cn An, Bn, Sn, Cn
1 An Bn, Sn, Cn An Bn, Sn, Cn
Initialized setting of parameter (Sn-03= 712)
Except the parameter of Sn-0102 and Sn-61, the parameter groups of An-□□,
Bn-□□, Cn-□□ and Sn-□□ can be initialized as factory setting according to
the different input voltage. At the same time, the terminal gj
can be set as 2-
wire or 3-wire operation mode under different setting of Sn-03. Please see 2-/3-
wire operation mode on page 81.
(4) Run Source Selection (Sn-04)
The parameter is used to select the source of run command.
Sn-04 = 0 : digital operator
1 : control circuit terminal
2 : RS-485 communication
If Sn-04 is set as 1, the run source is from the control circuit terminal. Under the
initial setting of 2-wire operation (through setting of Sn-03=7 or 9 or 11), the run
source will be FWD/STOP, REV/STOP.
If Sn-04 is set as 1, the run source is from the control circuit terminal. Under the
initial setting of 3-wire operation (through setting of Sn-03=8 or 10 or 12), the run
source will be RUN, STOP, FWD/ REV.
For more details, see “2-/3- wire operation” on page 81.
(5) Frequency Command Setting Method Selection (Sn-05)
The parameter is used to select the source of frequency command.
Sn-05 = 0 : digital operator
1 : control circuit terminal
2 : RS-485 communication
(6) Stopping Method Selection (Sn-06)
Setting the stopping method used when a stop command is executed.
Setting Function
0 Deceleration to stop
1 Coast to stop
2
DC braking stop: Stops faster than coast to stop, without regenerative
operation.
3 Coast to stop with timer: Run sources are disregarded during decel. time.