(23) Motor Overload Protection Selection (Sn-23)
Sn-23 = 0: Electronic overload protection disable.
Sn-23 = 1~4 : Electronic overload protection enabled. The electronic thermal
overload is detected according to the characteristic curves of
protection operating time. vs. motor rated current setting (Cn-09).
Sn-23 = 1 :The overload is detected according to the standard motor cold start curve.
= 2 : The overload is detected according to the standard motor hot start curve.
= 3 : The overload is detected according to the specific motor cold start curve.
= 4 : The overload is detected according to the specific motor hot start curve.
Disable the motor protection function (setting 0) when 2 or more motors are
connected to a single inverter. Use another method to provide overload protection
separately to each motor, such as connecting a thermal overload relay to the power
line of each motor.
The motor overload protection function should be set as Sn-23= 2 or 4 (hot start
protection characteristic curve) when the power supply is turned on or off frequently,
because the thermal values is reset each time when the power is turned off.
For the motor without forced cooling fan, the heat dissipation capability is lower
when in the low speed operation. The setting Sn-23 can be either ‘1’ or ‘2’.
For the motor with forced cooling fan, the heat dissipation capability is not
dependent upon the rotating speed. The setting Sn-23 can be either ‘3’ or ‘4’.
To protect the motor from overload by use of electronic overload protection, be
sure to set the parameter Cn-09 according to the rated current value shown on the
motor nameplate.
Cold Start
Low Speed
(<60 Hz)
Hot Start
High Speed
(>60 Hz)
100% 150% 200%
Motor Load Current (%)
(Cn-09 = 100%)
5.5
3.5
Overload Protect Time (min)
Fig. 37 Motor overload protection curve (Cn-09 setting = 100%)
(24)
Frequency Characteristics Command Selection at External Analog Input Terminal (Sn-24)
Sn-24= 0 : Frequency command is input at VIN terminal (0~10V)
= 1 : Frequency command is input at AIN terminal (4~20mA)
= 2 : Frequency command is the addition (VIN + AIN) at VIN (0~10V) and
AIN (4~20mA) terminal.
= 3 : Frequency command is the combination (VIN - AIN) at VIN (0~10V)
and AIN (4~20mA) terminal. If the value (VIN - AIN) is negative, the
reference command will take ‘0’ as a result.