(30) Multi-Function Output Terminal (RA-RB-RC or R1A-R1B-R1C) Function Selection (Sn-30)
(31) Multi-Function Output Terminal (DO1-DOG) Function Selection (Sn-31)
(32) Multi-Function Output Terminal (DO2-DOG or R2A-R2C) Function Selection (Sn-32)
Multi-function output terminal setting and its function as shown in Table 16.
Table 16 Multi-function output terminal function
Setting
Function LCD Display Description
Ref.
Page
00 During running Running
ONDuring running
91
01 Zero speed
Zero Speed
ONZero speed
91
02 Frequency agree Frequency Arrive
Speed agree width: Cn-31
55
03 Setting frequency agree Agreed F Arrive
ONoutput frequency = ±Cn-29,
Speed agree width: Cn-31
55
04
Output frequency
detection1
Freq. Det. 1
ONwhile ACC, -Cn-29output freq.Cn-29
while DEC, -Cn-30output freq.Cn-30
Speed agree width: Cn-31
55
05
Output frequency
detection2
Freq. Det. 2
ONwhile ACC, output freqCn-29(or-Cn-29)
while DEC, output freqCn-30(or-Cn-30)
Speed agree width: Cn-31
55
06 Inverter ready Run Ready OK!
ONREADY
91
07 Undervoltage detected Low Volt Detect
ONUndervoltage detected
91
08 Output baseblocked Output B.B.
ONOutput baseblocked
91
09 Run source mode
Run Source
Operator
ON
Run source from digital operator (Local mode)
91
10 Frequency command mode Ref. Cmd. Operator
ONFrequency command from digital operator
(Local mode)
91
11 Overtorque detected Over Tq. Detect
ONOvertorque detected
56,76
12
Frequency command
Invalid
Freq. Cmd. Invalid
ONFrequency command Invalid
92
13 Fault Fault
ONFault
92
14 Pulse signal output Pulse Mul. Output Only set by Sn-31, Sn-32 (terminal DO1-DOG) 92
15 Undervoltage alarm Low Volt Alarm
ONUndervoltage alarm
92
16 Inverter overheat Inverter Over Heat
ONInverter Overheat
106
17 Motor overload Motor Over Load
ONMotor Overload
79
18 Inverter Overload Inverter Over Load
ONInverter Overload
106
19 Fault retry Fault Retry
ONRetry
52
20
RS-485 communication
fault
RS-485 Fault
ONRS-485 communication fault
106
21 Timer function output Timer Function Signal delay output (.vs. timer function input) 44,93
22
RS-485 Communication
Application
Comm. Control
Extension Output Contact application
(Please refer to ‘7200MA RS-485 MODBUS
/PROFIBUS Application Manual’)
93