Error Causes Action to Be Taken
•
Input voltage drop
Measure the main circuit DC volta
e is lower allowance level, re
ulate the
input voltage.
•
Input voltage rise
Measure the main circuit DC volta
her than allowance level, re
ulate
the input voltage.
•
Overload
•
Cooling fan fault. Ambient temperature rises.
•
Clogged filter.
Check for the fan, filter and the ambient
temperature.
•
Machine error or overload
•
Check the use of the machine.
•
Set a higher protection level (Cn-32).
•
Insufficient Accel./Decel. Time
•
Overload
•
Excessive load impact occurs while operating
•
Increase Accel./Decel. Time.
•
Check the load.
•
Operation sequence error
•
3-wire/2-wire selection error
•
Check the circuit of system
arameters Sn-25,
26, 27, and 28.
•
External noise
•
Excessive vibration or impact on Communication wire
•
Not properly contacted
•
Check the parameter setting, including Sn-01, Sn-02.
•
Check if the comm. wire is not properly contacted.
•
Restart, if fault remains, please contact to us.
erator and inverter has not been
established after system starts for 5 seconds.
Communication is established after s
stem starts, but
transmission fault occurs for 2 seconds.
•
Re-plug the connector of the digital operators.
•
Replace the control board.
•
External B.B. signal is input.
nal is removed, execute the
speed search of the inverter.
•
Inverter KVA setting error.
er KVA value. Be aware of the
difference of 220V and 440V
The value of Sn-25~Sn-28 is not in ascendin
Ex.
Sn-25= 05, Sn-28= 02, those are improper setting).
•
Set speed search command of 21 and 22 simultaneously.
the value of Sn-25
must be smaller than those of Sn-26, 27, 28)
•
Command 21 and 22 can not be set on two multi-
function-input contacts simultaneously.
•
The values of Cn-02~Cn-08 do not satisfy
F
max
≥
F
A
≥
F
B
≥
F
min
.
•
Change the settings.
•
Upper limit and lower limit setting is incorrect.
•
Change the settings.
ue
protection level.
•
The circuit of PG is not properly connected or open-
circuit.
•
Check the wiring of PG.
ue
protection level.
•
Bad communication during operator and inverter.
•
The connector is not properly connected.
•
Check if the connector is not properly connected.
•
Operator EEPROM error.
•
Disable load function of operator.
•
Replace the operator.
•
Incorrect inverter data format
•
Communication noise.
•
Download the data to the operator again.
•
Check if the connector is not properly connected.
•
Communication noise
•
Check if the connector is not properly connected.
between inverter and motor is disconnected.
•
Motor load unbalance.
Correct the inverter/motor ca