46
Function
Parameter
No.
Name LCD display (English) Setting range
Setting
Unit
Factory
Setting
Ref.
Page
Cn-45 PG Parameter
Cn-45= 0000.0
PG Parameter
0.0∼3000.0P/R 0.1P/R 0.0P/R
Cn-46 Pole no. of Motor
Cn-46= 04P
Motor Pole
2∼32P 2P 4 P
Cn-47
ASR Proportional
Gain 1
Cn-47= 0.00
ASR Gain 1
0.00∼2.55 0.01 0.00
Cn-48 ASR Integral Gain 1
Cn-48= 01.0s
ASR Intgl. Time 1
0.1∼10.0S 0.1s 1.0s
Cn-49
ASR Proportional
Gain 2
Cn-49= 0.02
ASR Gain 2
0.00∼2.55 0.01 0.02
Cn-50 ASR Integral Gain 2
Cn-50= 01.0s
ASR Intgl. Time 2
0.1∼10.0S 0.1s 1.0s
60
Cn-51 ASR Upper Bound
Cn-51= 05.0%
ASR Up Bound
0.1∼10.0% 0.1% 5.0%
Cn-52 ASR Lower Bound
Cn-52= 00.1%
ASR Low Bound
0.1∼10.0% 0.1% 0.1%
Cn-53
Excessive Speed
Deviation Detection
Level
Cn-53= 10%
Sp.Deviat. Det.Level
1∼50% 1% 10%
Speed
feedback
control
Cn-54
Overspeed Detection
Level
Cn-54= 110%
Over Sp.Det. Level
1∼120% 1% 110%
60
Cn-55
PID Integral Upper
Bound
Cn-55= 100%
PID I-Upper
0∼109% 1% 100%
PID
Control
Cn-56
PID Primary Delay
Time Constant
Cn-56= 0.0s
PID Filter
0.0∼2.5s 0.1s 0.0s
61
Cn-57
Motor Line-to-Line
Resistance (R1)
Cn-57= 02.233Ω
Mtr LINE_R
0.001∼60.000Ω 0.001Ω
2.233
Ω
*4
Cn-58
Motor Rotor Equivalent
Resistance
(R2)
Cn-58= 01.968Ω
Mtr ROTOR_R
0.001∼60.000Ω 0.001Ω
1.968
Ω
*4
Cn-59
Motor Leakage
Inductance (Ls)
Cn-59= 9.6mH
Mtr LEAKAGE_X
0.01∼200.00mH
0.01mH 9.6mH
*4
Cn-60
Motor Mutual
Inductance (Lm)
Cn-60= 149.7mH
Mtr MUTUAL_X
0.1∼6553.5mH
0.1mH
149.7mH
*4
Sensorless
Vector
Control
Cn-61
Slip Compensation
Gain
Cn-61= 1.00
SLIP GAIN
0.00∼2.55 0.01 1.00
61,
62
*1 These are for a 220V class inverter. Value(*1) for a 440V class inverter is double.
*2 These are for a 220V class inverter. Value(*2) for a 440V class inverter is double.
*3 The setting range is 10% ~200% of the inverter rated current.
*4 The factory setting values will vary based upon the inverter capacity selection (Sn-01)
value. In this case, the setting is for 4-pole, 220V, 60Hz, 1Hp TECO standard induction