EasyManua.ls Logo

TECO speecon 7200ma - Control Parameters: Sensorless Vector Control; Sensorless Vector Control Parameters (Cn-45 to Cn-61)

TECO speecon 7200ma
128 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
46
Function
Parameter
No.
Name LCD display (English) Setting range
Setting
Unit
Factory
Setting
Ref.
Page
Cn-45 PG Parameter
Cn-45= 0000.0
PG Parameter
0.03000.0P/R 0.1P/R 0.0P/R
Cn-46 Pole no. of Motor
Cn-46= 04P
Motor Pole
232P 2P 4 P
Cn-47
ASR Proportional
Gain 1
Cn-47= 0.00
ASR Gain 1
0.002.55 0.01 0.00
Cn-48 ASR Integral Gain 1
Cn-48= 01.0s
ASR Intgl. Time 1
0.110.0S 0.1s 1.0s
Cn-49
ASR Proportional
Gain 2
Cn-49= 0.02
ASR Gain 2
0.002.55 0.01 0.02
Cn-50 ASR Integral Gain 2
Cn-50= 01.0s
ASR Intgl. Time 2
0.110.0S 0.1s 1.0s
60
Cn-51 ASR Upper Bound
Cn-51= 05.0
ASR Up Bound
0.110.0 0.1 5.0%
Cn-52 ASR Lower Bound
Cn-52= 00.1
ASR Low Bound
0.110.0 0.1 0.1%
Cn-53
Excessive Speed
Deviation Detection
Level
Cn-53= 10
Sp.Deviat. Det.Level
150 1 10%
Speed
feedback
control
Cn-54
Overspeed Detection
Level
Cn-54= 110
Over Sp.Det. Level
1120% 1 110%
60
Cn-55
PID Integral Upper
Bound
Cn-55= 100
PID I-Upper
0109 1 100%
PID
Control
Cn-56
PID Primary Delay
Time Constant
Cn-56= 0.0s
PID Filter
0.02.5s 0.1s 0.0s
61
Cn-57
Motor Line-to-Line
Resistance (R1)
Cn-57= 02.233Ω
Mtr LINE_R
0.00160.000Ω 0.001Ω
2.233
Ω
*4
Cn-58
Motor Rotor Equivalent
Resistance
(R2)
Cn-58= 01.968Ω
Mtr ROTOR_R
0.00160.000Ω 0.001Ω
1.968
Ω
*4
Cn-59
Motor Leakage
Inductance (Ls)
Cn-59= 9.6mH
Mtr LEAKAGE_X
0.01200.00mH
0.01mH 9.6mH
*4
Cn-60
Motor Mutual
Inductance (Lm)
Cn-60= 149.7mH
Mtr MUTUAL_X
0.16553.5mH
0.1mH
149.7mH
*4
Sensorless
Vector
Control
Cn-61
Slip Compensation
Gain
Cn-61= 1.00
SLIP GAIN
0.002.55 0.01 1.00
61,
62
*1 These are for a 220V class inverter. Value(*1) for a 440V class inverter is double.
*2 These are for a 220V class inverter. Value(*2) for a 440V class inverter is double.
*3 The setting range is 10% ~200% of the inverter rated current.
*4 The factory setting values will vary based upon the inverter capacity selection (Sn-01)
value. In this case, the setting is for 4-pole, 220V, 60Hz, 1Hp TECO standard induction
motors.

Table of Contents