Syntax and Commands
3-106 AFG3000 Series Arbitrary/Function Generators Reference Manual
TRIGger[:SEQuence]:TIMer
This command sets or queries the period of an internal clock when you select the
internal clock as the trigger source with the TRIGger[:SEQuence]:SOURce
command.
Group
Trigger
Related Commands
TRIGger[:SEQuence]:SOURce
Syntax
TRIGger[:SEQuence]:TIMer <seconds>
TRIGger[:SEQuence]:TIMer?
Arguments
<seconds>::=<NRf>[<units>]
where
<units>::=[µs | ms | s]
Returns
<seconds>
Examples
TRIGger:SEQuence:TIMer 5ms
sets the internal trigger rate to 5 ms.
TRIGger[:SEQuence][:IMMediate] (No Query Form)
This command forces a trigger event to occur.
Group
Trigger
Syntax
TRIGger[:SEQuence][:IMMediate]
Arguments
None
Examples
TRIGger:SEQuence:IMMediate
generates a trigger event.