TSA-200 / TSA-200XT / TSA-240 / TSA-240XT
© 2010 – 2014 Telefire Fire & Gas Detectors Ltd Revision 1.06 July 2014
Page 20 of 79
Keyboard input .............................................................. Manual Only (keyboard switch
on the front panel)
EM1 Outputs
Output 3 ........................................................................ Extinguisher, not silenceable
Output 4 ........................................................................ Extinguishing (EVAC)
Strb/Sounder, not silenceable
Timing parameters
Extinguishing Delay ............................................... 0 seconds (No Delay)
Extinguisher Pulse Duration ................................... 20 seconds
Manual Release Delay ........................................... No Delay
Alarm Delay (AVF) ................................................. 30 seconds
Alarm Confirmation Period………………………..…120 Seconds
Default Passwords: Access level 2 PW is 1111, default level 3 PW is 2222