TSA-200 / TSA-200XT / TSA-240 / TSA-240XT
© 2010 – 2014 Telefire Fire & Gas Detectors Ltd Revision 1.06 July 2014
– Page 17 of 53 –
ITEM RATING REMARKS COMMUNICATION
PARAMETERS
EM1 Ver. 1.1 out 4,
Extinguishing/Evacuation Sounder
Level Act. 24V DC, 1.0A max, continuous Flashes in Activated state. ON
in Released state,
Modulated DC
Number of sounders Dependent on current consumption See detailed explanation
GENERAL
Input nominal quiescent voltage,
current
23.0V, 5.0mA Current Limit
Terminal block wire capacity 12-18 AWG
Max number of detectors per zone 32
Number of detection zones 2
Total MAX number of detectors 64,
Recommended cable parameters SEE "INSTALLATION", page 23
Table 1 Technical Specifications
i
Note
The TSA-200 product family MAX number of detectors per zone is 32
The TSA-200 / TSA-200XT Total MAX number of detectors is 64 (In a two
zones configuration)
The TSA-240 / TSA-240XT Total MAX number of detectors is 128 (In a four
zones configuration)