TSA-200 / TSA-200XT / TSA-240 / TSA-240XT
© 2010 – 2014 Telefire Fire & Gas Detectors Ltd Revision 1.06 July 2014
– Page 13 of 53 –
7.3 Table of Technical Specifications, TSA-200 product family
ITEM RATING REMARKS COMMUNICATION
PARAMETERS
MECHANICAL
Dimensions (W / H / D)
320 / 245 / 90 mm
Weight (excluding batteries)
3.0 Kgm.
ENVIRONMENTAL
Operating Temperature range
-5°C ÷ +40°C, Max RH 95% (3k5) Non condensing
IP rating
30
POWER RATINGS
Mains Supply 85 ~ 264Vac, 47 ~ 63Hz From Data Sheet
Mains Supply Current (Typical) 0.75A/115Vac, 0.5 A/230Vac From Data Sheet
Mains Supply Fuse Not Applicable No user serviceable parts
Power Supply output rating, 36W From Data Sheet
Total output current 1.5A electronic current limit From Data Sheet
Max Ripple& Noise Voltage 28V & Charger out: 200mVp-p
Battery Type Two 12V 5AH connected in series Yuasa NP 12-5 or equivalent
Battery Charge Voltage 27.3V±0.5V Modulated DC
Battery Charge Current 0.3A max. Electronically limited