EasyManua.ls Logo

Telefire TSA-200XT - Connecting the Mains Power and Batteries; Figure 7 Typical Fire Alarm, (Non Extinguishing) Connections

Default Icon
79 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
TSA-200 / TSA-200XT / TSA-240 / TSA-240XT
© 2010 – 2014 Telefire Fire & Gas Detectors Ltd Revision 1.06 July 2014
Page 30 of 79
9.7.1 Typical Fire Alarm, Non Extinguishing Connections
Figure 7 Typical Fire Alarm, (Non Extinguishing) Connections
The figure above shows a typical, Fire Detection and Alarm, TSA-200 application.
i
Note
THIS IS A NON EXTINGUISHING EXAMPLE!
The EM1 module is not shown.
It shows the TSA-200 Main Board connected to two zones, where in each zone
detectors and Manual Call Points (MCP) are shown. Also shown is a Fire Alarm Device
(alarm sounder, typically a horn), battery input lines and other lines are omitted for
clarity.
9.8 Connecting the Mains Power and Batteries
SEE SAFETY, page 9
SEE Routing cables into the ECD and maintaining the protection level, page 9.
9.8.1 Connecting AC power and ground wires
Connect the control panel’s AC input cable directly to a dedicated circuit breaker that is
not shared by other appliances or equipment. It is recommended that the circuit breaker
shall be labeled “FIRE ALARM”.
Use a three wire cable (Line, Neutral and Ground wires) of the appropriate gauge and
colors

Table of Contents

Related product manuals