TSA-200 / TSA-200XT / TSA-240 / TSA-240XT
© 2010 – 2014 Telefire Fire & Gas Detectors Ltd Revision 1.06 July 2014
Page 33 of 79
10 Post-Installation
10.1 Configuring the Control Panel
The ECD is delivered in a default configuration (see Default Ports Allocation and ECD
Configuration, page 19.)
Modify only if necessary, by programming the ECD, as explained in Control Panel
Configuring and Programming, page 57
10.2 Field Test
Perform a field test – this test allows a single operator to perform a test for all field
devices, including detectors, call points, and other inputs.
The testing process is automatic except for activation of the device which is done
manually by means specified by the device's manufacturer.
Telefire's devices can be tested by putting a magnet to the test point of the detectors or
activation of the call points through the testing tool (supplied with the call point).
10.3 Outputs Test
Test the outputs of the system to ensure that they are activated properly
10.4 Arming the Extinguishing device
Arm the extinguishing devices.
i
Note
The Control and Indicating Equipment (CIE) is now fully functional, and, with
the proper alarm conditions, the extinguisher will be activated.
10.5 Change Password
It is recommended to change the system's passwords from their default values after
completing the installation and system testing. See Changing the Password, page 62
!
Warning
If the passwords are changed from their default values and then
forgotten or lost, A factory reset is required: if you lose or forget the
password, the panel must be sent back to the factory to be reset. There
is no field option for gaining access to the panel without a valid
password.
Once you have changed the password, it is important that you write it
down somewhere and store it in a known and safe place.
10.6 System Additional Documentation
Attach the followings to the system’s front panel, or place it in a prominent position
nearby:
A list of areas/zones as installed in the protected premises
Actions to be taken by the operator upon events of alarm or fault